Cetetherm AquaEfficiency
Installation, service and operating instruction
61
18.4 Change fuses
The control box is fitted with a set of fuses to protect the different components against overload.
Extra fuses are included in the control box.
The service work must be carried out by an authorized service technician.
Turn off the power supply before starting to work.
1
Fuse FU5
3
Led 1-4, lit when pump P1- P4 is power supplied
2
Fuse FU1
– FU4
For technical information about the fuses, see
18.5
Pumps’ number
The pumps’ configuration and connections are factory made.
In a service situation the correct pump must be identified.
Codification Meaning
Connected pump(s)
FIxxxIS
I
nstantaneous
S
ingle
P1
FIxxxID
I
nstantaneous
D
ouble
P1+P2
FIxxxSS
Semi-instantaneous
S
ingle /
S
ingle
P1+P3
FIxxxDS
Semi-instantaneous
D
ouble /
S
ingle
P1+P2+P3
FIxxxxDD
Semi-instantaneous
D
ouble /
D
ouble
P1+P2+P3+P4
18.6 Add a recycling pump to an AquaEfficiency Direct
A recycling pump can be added to an AquaEfficiency Direct. The pump must be connected to P3.