CET Electric Technology
90
4)
Analog Value Objects (PMC-53A-E’s Basic Setup Registers)
Optional Properties Supported: Description, Relinquish_Default, Priority_Array
Writable Properties: Present_Value, Out_Of_Service, Units, Relinquish_Default
Use the Present Value property of the Analog Value object for some writable variables in the meter
other than those used specifically for BACnet configuration or Time Synchronization. Values are
checked when written, and errors are returned for invalid entries. The table below describes how
the Setup Registers of the PMC-53A-E are represented in BACnet, their valid ranges, their defaults
as well as how they are used. PMC-53A-E supports the Description, Relinquish_Default and
Priority_Array optional properties. Writable properties include Present_Value, Out_Of_Service,
Units and Relinquish_Default, but Units are not non-volatile after modification.
Register
Description
Property
Unit/ Range
Default/Note
AV 6000
PT Primary High
#
R/W
0 to 1000 kV
0
AV 6001
PT Primary Low
#
R/W
1 to 999 V
100
AV 6002
PT Secondary
#
R/W
1 to 690
100
AV 6004
CT Primary
R/W
1 to 30000
5
AV 6006
CT Secondary
R/W
1 to 5
5
AV 6012
I4 Primary
R/W
1 to 30000
5
AV 6014
I4 Secondary
R/W
1 to 5
5
AV 6020
Wiring Mode
R/W
0 = DEMO
1 = 1P2W L-N
2 = 1P2W L-L
3 = 1P3W L-L-N
4 = 3P3W, 5 = 3P4W
5
AV 6021
PF Convention
R/W
0 = IEC, 1 = IEEE, 2 = -IEEE
0
AV 6022
kVA Calculation
R/W
0 = Vector, 1 = Scalar
0
AV 6028
THD Calculation
R/W
0 = THDf, 1 = THDr
0
AV 6029
Demand Period
R/W
1 to 60 min
15
AV 6030 Number of Sliding Windows
R/W
1 to 15
1
AV 6047
Interval Energy Period
R/W
5 to 60 min
60
AV 9603 Clear Present Peak Demand
W
65280
Default = 0
Writing “0xFF00”
to the register to
execute the
described action.
AV 9601
Clear Energy
W
AV 9610
Clear DI #1 Counter
W
AV 9611
Clear DI #2 Counter
W
AV 9612
Clear DI #3 Counter
W
AV 9613
Clear DI #4 Counter
W
#
PT Primary / PT Secondary Must be less than 10000.
5)
Binary Input Objects (PMC-53A-E’s Digital Inputs)
Optional Properties Supported: Description, Reliability
Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential
concern regarding system measurements. These objects support the Description and Reliability
optional properties and all required Binary_Input object properties. None of them are writable.
Register
Description
Property
Note
BI0
DI 1
R
0 = Inactive, 1 = Active
BI1
DI 2
R
0 = Inactive, 1 = Active
BI2
DI 3
R
0 = Inactive, 1 = Active
BI3
DI 4
R
0 = Inactive, 1 = Active
6)
Binary Output Objects (PMC-53A-E’s Digital Outputs)
Optional Properties Supported: Inactive_Text, Active_Text
Use the Present_Value property of the Binary_Output objects as alerts for DO conditions. Reading
Binary_Output objects have the highest priority. PMC-53A-E supports Inactive_Text, Active_Text
optional properties and all required Binary_Output object properties. Present_Value,
Out_Of_Service and Polarity properties can be written, but these are non-volatile after
modification. The Present_Value can only be written when the Out_Of_Service is true to change
the state of the Digital Output and will be written as W when the Out_Of_Service is false.
Register
Description
Property
Note
BO0
DO 1
R/W
0 = Inactive, 1 = Active
BO1
DO 2
R/W
0 = Inactive, 1 = Active