background image

Revision Date: April 18, 2019

 

PMC-340 Quick Start Guide 

Version 1.1 

Package Contents 

a.

 

PMC-340 Meter with all installation clips and plug-in connectors installed          b. Factory Test Report                           

c.   CD with PMC-340 User Manual       

d. 1×120Ω Termination Resistor 

e.

 

Quick Start Guide (this document) 

Meter Overview 

 

 

Front View of PMC-340

     

           

 

  Direct Input                   

CT Input 

Serial Number Label 

Warning Label 

Using the Front Panel Buttons 

Buttons 

Data Display Mode 

Setup Configuration Mode 

<

>

 

The Default Display shows the kWh Import measurement 
under the Energy menu. Pressing this button scrolls 
through the available measurements in this menu. 

  

While at a particular menu, pressing this button scrolls 
through the available measurements. 

Before an item is selected, pressing this button scrolls to the 
next setup parameter. If the selected parameter is a numeric 
value, pressing this button increments the selected digit. If the 
selected parameter is an enumerated value, pressing this 
button scrolls through the selection list. 

<

>

 

Pressing this button at any time while in Data Display 
mode will jump to the next available menu item 
depending on where the display is at the time. 

  

For example, if the display currently shows Ib under the 
U/I menu, pressing <

> now will immediately jump to 

the Power menu. 

Pressing this button for two seconds toggles between Data 
Display 
mode and Setup Configuration mode. Once inside the 
Setup Configuration mode, pressing this button selects a 
parameter for modification. Once selected, the parameter 
value blinks while it’s being changed.   

  

If the selected parameter is a numeric value, the cursor is at 
the right most digit by default. Pressing this button moves the 
cursor one position to the left. Once the cursor has reached 
the left most digit, pressing this button again will save the 
current numeric value into memory. 

Mounting the Meter 

 

Before installation, make sure that the DIN rail is already in place 

 

Move the installation clips at the back of the PMC-340 downward 
to the “unlock” position 

 

Align the top of the mounting channel at the back of the PMC-340 
at an angle against the top of the DIN rail as shown in figure right 

 

Rotate  the  bottom  of  the  PMC-340  towards  the  back  while 
applying  a  slight  pressure  to  make  sure  that  the  device  is 
completely and securely fixed on to the DIN rail 

 

Push the installation clips upward to the “lock” position to secure 
the PMC-340 on to the DIN Rail 

 

 

 

Terminal

 

Description

 

A

 

L1, L2, L3, N

 

L1, L2, L3, N from Source

 

B

 

1, 2, 3, 4

 

Voltage Inputs: V1, V2, V3, VN (CT Inputs Option only)

 

5, 6

 

Pulse Outputs: +, -

 

D

 

-

 

LCD Display

 

-

 

Energy Pulse and Comm. Indicators

 

F

 

-

 

Buttons

 

G

 

7, 8, 9, 10

 

Digital Inputs: DIC, DI1, DI2, DI3 (PMC-340B only)

 

H

 

11, 12

 

RS-485: D+, D-

 

I

 

L1, L2, L3, N

 

L1’, L2’, L3’, N’ to Load

 