Appendix C – SOE Event Classification
Event
Classification
Sub-
Classification
Event Value
Scale/Option
Description
1=DI Changes
1
1 / 0
DI1 Close/DI1 Open
2
1 / 0
DI2 Close/DI2 Open
3
1 / 0
DI3 Close/DI3 Open
4
1 / 0
DI4 Close/DI4 Open
5
1 / 0
DI5 Close/DI5 Open
6
1 / 0
DI6 Close/DI6 Open
2=DO Changes
1
1 / 0
DO1 Operated/Released by Remote Control
2
1 / 0
DO2 Operated/Released by Remote Control
3
1 / 0
DO3 Operated/Released by Remote Control
4
1 / 0
DO1 Operated/Released by Setpoint
5
1 / 0
DO2 Operated/Released by Setpoint
6
1 / 0
DO3 Operated/Released by Setpoint
7
1 / 0
DO1 Operated/Released by Dip/swell
8
1 / 0
DO2 Operated/Released by Dip/swell
9
1 / 0
DO3 Operated/Released by Dip/swell
10
1 / 0
DO1 Operated/Released by Transient
11
1 / 0
DO2 Operated/Released by Transient
12
1 / 0
DO3 Operated/Released by Transient
13
0
DO1 Released by Pulse Time Out
14
0
DO2 Released by Pulse Time Out
15
0
DO3 Released by Pulse Time Out
16
1 / 0
DO1 Operated/Released by Front Panel
17
1 / 0
DO2 Operated/Released by Front Panel
18
1 / 0
DO3 Operated/Released by Front Panel
3=Setpoint
1
Trigger Value (x100)
Over Uln Setpoint Active
2
Trigger Value (x100)
Over Ull Setpoint Active
3
Trigger Value (x1000)
Over Current Setpoint Active
4
Trigger Value (x1000)
Over I4 Setpoint Active
5
Trigger Value (x100)
Over Freq. Deviation Setpoint Active
6
Trigger Value
Over kW Total Setpoint Active
7
Trigger Value
Over kvar Total Setpoint Active
8
Trigger Value (x1000)
Over PF Total Setpoint Active
9
1
DI1 Close Setpoint Active
10
1
DI2 Close Setpoint Active
11
1
DI3 Close Setpoint Active
12
1
DI4 Close Setpoint Active
13
1
DI5 Close Setpoint Active
14
1
DI6 Close Setpoint Active
15
Trigger Value
Over AI Setpoint Active
16
Trigger Value
Over kW Total Demand Setpoint Active
17
Trigger Value
Over kvar Total Demand Setpoint Active
18
Trigger Value (x1000)
Over PF Total Demand Setpoint Active
19
Trigger Value
Over kW Total Predicted Setpoint Active
20
Trigger Value
Over kvar Total Predicted Setpoint Active
21
Trigger Value (x1000)
Over PF Total Predicted Setpoint Active
22
Trigger Value (x100)
Over Voltage THD Setpoint Active
23
Trigger Value (x100)
Over Voltage TOHD Setpoint Active
24
Trigger Value (x100)
Over Voltage TEHD Setpoint Active
25
Trigger Value (x100)
Over Current THD Setpoint Active
26
Trigger Value (x100)
Over Current TOHD Setpoint Active
27
Trigger Value (x100)
Over Current TEHD Setpoint Active
28
Trigger Value (x10)
Over U2 Unbalance Setpoint Active
29
Trigger Value (x10)
Over I2 Unbalance Setpoint Active
30
Trigger Value (x100)
Over Voltage OverDeviation Setpoint Active
31
1
Over Voltage Phase Reversal Setpoint Active
32
Trigger Value (x1000)
Over Ir Setpoint Active
33
Trigger Value (x100)
Over U2 (Negative Sequence Voltage) Setpoint Active
34
Trigger Value (x100)
Over U0 (Zero Sequence Voltage) Setpoint Active
35
1
Over Current Phase Reversal Setpoint Active
36~45
-
Reserved
46
Return Value (x100)
Over Uln Setpoint Return
47
Return Value (x100)
Over Ull Setpoint Return
48
Return Value (x1000)
Over Current Setpoint Return
49
Return Value (x1000)
Over I4 Setpoint Return
50
Return Value (x100)
Over Freq. Deviation Setpoint Return
51
Return Value
Over kW Total Setpoint Return
52
Return Value
Over kvar Total Setpoint Return
53
Return Value (x1000)
Over PF Total Setpoint Return
54
0
DI1 Close Setpoint Return
55
0
DI2 Close Setpoint Return
56
0
DI3 Close Setpoint Return
57
0
DI4 Close Setpoint Return
58
0
DI5 Close Setpoint Return
59
0
DI6 Close Setpoint Return
60
Return Value
Over AI Setpoint Return
61
Return Value
Over kW Total Demand Setpoint Return
62
Return Value
Over kvar Total Demand Setpoint Return
63
Return Value (x1000)
Over PF Total Demand Setpoint Return