C300R User Manual
Page 18
SETTINGS MENU
The LCD display can be used to access detailed information about the current UPS status as well as configure the
UPS settings.
The UPS is controlled using basic button functions via the LCD panel, to access and configure the UPS
•
Press and hold the Enter button
for longer than 3 seconds. This will cause the UPS to go into settings
mode.
•
Press the Select button
to cycle through the setting items shown in the table below.
•
When the LCD displays the setting that requires amendment, press the enter button
for longer than one
second to enter the option and amend the value.
•
Press the Select button
to select the value of the setting.
•
Press and hold the Enter button for one second, the UPS will then return to settings mode.
•
Press and hold the Enter button
for 3 seconds or the power button
for 0.5 seconds to exit settings
mode
LCD DISPLAY
DISPLAY MEANING
SETTINGS
OPV
Output voltage mode selection
[220]= 220V
[230]= 230V
[240]= 240V
AVR
Input type selection
[000]= Normal range mode
[001]= Wide range mode
[002]= Generator mode
EbM
External battery module (EBM) settings
0~9 is the number of external battery module(s)
TEST
Auto self-test function
[000]=Disable[001]=Enable
AR
Automatic restart
[000]=Disable[001]=Enable
GF
Green function
[000]=Disable[001]=Enable
bZ
Buzzer control
[000]=Disable[001]=Enable
LS1
Load segment 1
[000]=Turn off[001]=Turn on
LS2
Load segment 2
[000]=Turn off[001]=Turn on
BY DEFAULT, THE LCD WILL DISPLAY THE UPS STATUS SUMMARY SCREEN.