2.13
Grounding the IP-10C
1 On the front side of each IP-10C, loosen the nut, plain washer, and serrated
washer.
2 Place the cable lug (supplied with the IP-10C housing kit) on the screw.
3 Secure the cable lug.
IP-10C Grounding Cable
The unit’s earthing screw terminal shall be permanently connected to
protective earth in a building installation in accordance with applicable
national code and regulations by a service person.
A 2-Pole circuit breaker, a branch circuit protector, suitably certified in
accordance with applicable national code and regulations, rated maximum
20A, shall be installed for full power disconnection in a building
installation.
Any outdoor antenna cable shield shall be permanently connected to
protective earth in a building installation.
When selecting a power source, the following must be considered:
DC power can be from -40 VDC to -60 VDC.
Recommended:
Availability of a UPS (Uninterrupted Power Source),
battery backup, and emergency power generator.
Whether or not the power source provides constant power (i.e., power is
secured on weekends or is shut off frequently and consistently).
The power supply must have grounding points on the AC and DC sides.
Caution!
The user power supply GND must be connected to the positive pole in the IP-10C
power supply. Any other connection may cause damage to the system!
Important:
For the warranty to be honored, you must install the IP-10C
in accordance with the instructions above.
!!