Page 44
22. SECTOR controller features
Menu 2 - Safety (collision force)
!
Collision force
The collision force can be set independently for raising or lowering from
minimum to maximum in five discrete steps. A sixth step will disable collision
sensing entirely, allowing maximum force to be achieved. The motor will only
shut down when its stall point is reached. Stall level is adjustable, refer to
Torque Limit under Menu 5.
The response of the system to a collision will vary, depending on the Operating
Standard (eg. CE, UL325 ) selected
Collision force setting satisfies UL325, but the SECTOR barrier itself is not certified
The maximum force setting should only be used if additional safety
measures are taken, for example, inductive loops, etc.
!
!
!
Collision count
The number of sequential collisions that the system will allow, before shutting
down the controller, if the boom pole does not reach the lowered position.
Counter resets each time the boom pole reaches lowered position. A valid
trigger input will clear the shutdown
Alarm output
An alarm is activated if the multiple collision shutdown is triggered. This menu
item configures the different alarm outputs
LCK as ESTOP
Allows the Lck (Holiday Lockout) input to be configured as an emergency stop
input
!
External boom status
The gate status indication can be used to drive an external device such as a
traffic light or Pillar Light by either producing a potential across the selected
indicator or switching a dry contact.
The following outputs can be configured as external indicators:
!
Pillar/Courtesy Light contact (potential-free normally-open contact, fuse
protected – 5A)
!
Safety beam common (this is an open collector drive, max current draw 3A,
not fuse protected)
!
Status LED output (operate up to three LEDs in parallel or interface with
multi-LED driver card, CP78)
!
Aux. I/O (this is an open collector drive, max current draw 3A, not fuse
protected)
The conditions under which the selected output must be active can be
configured according to the status of the gate, and more than one status can
be selected simultaneously:
!
Open indication