FI002K0018v1530hUK – THS/21 Instruction manual for installation, use and maintenance
5
MAINTENANCE
ORIGINAL
INSTRUCTION 195
Fault Message
Probable cause
Action
Type
EJECT CHECK FAULT
Product passed in front of the
Ejection Check photocell during
an ejection
Remove the product not ejected, reset and check the
ejector correct activation.
In case the ejection of a contaminated product is
correctly performed, adjust the diagnosis accuracy
(ECKA) according to the shape of the product in
transit.
Temporary activation of the
photocell during ejection
Sensor connected to EJECTION
CHECK input faulty or
disconnected
Check the sensor mechanical and electrical
installation and its correct activation
In absence of the installed sensor, deactivate the
diagnosis (ECK=OFF)
If the problem persists, contact Assistance Service.
FAIL-SAFE FAILED
One of the Tests of the Fail Safe
Test, is failed
Check the correct operation and programming of
involved sensors. After the reset it is possible to
perform the test again.
SYNC PHOTOC.FAULT
Synchronization photocell
obstructed or malfunctioning
according to the space limit set
on SPMA or to the limit value
PAT (with PAT>1)
Remove the obstruction condition or check the correct
functioning of the photocell
Check that there have been no contiguous packages
in transit
Check that the SPMA space limit is adequate for the
application and in any case greater than the length of
the package
Check that there have been no multiple spurious
readings from the Ejection Verification photocell and, if
needed, increase the PAT parameter value
Sensor connected to
PHOTOCELL input faulty or
disconnected
Check the sensor mechanical and electrical
installation and its correct activation
In absence of the installed sensor, deactivate the
diagnosis (SPMA=0)
If the problem persists, contact Assistance Service.
continue >>