3
FI002K0018v1530hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLAZIONE
128 ORIGINAL
INSTRUCTION
3.9.9.4 Automatic ejection (EM=F)
EM
Typical product
Throughput
Ejector Type
Ejection
Notes
F
Random packed product
Medium
throughput
Retracting belt, Drop
nose, Lift flap, Diverter
arm
Contaminated product
automatically ejected
-
Packed product
aligned in multiple files
Bulk material
Free-falling product
Operation with ejector activation for the ejection of contaminated material.
In CEIA Integrated Systems fitted with an ejector, this mode determines the automatic ejection and
removal of the contaminated material in the reject bin.
Programming menu
Remote
parameter
Description
Setting
Ejection
> Ejection mode
EM
Automatic removal of contaminated material
with alarm synchronization
F
Ejection
> Ej. distance
ED
Distance of ejection area from the centre of the
Probe
0 - 6000 mm
Ejection
> Ejection time
ET
Ejection relay minimum activation time
0.01 - 120.00 s
Example with retractable
belt
S: Metal Detector Probe
N: Conveyor belt
C: Contaminated product
DW: Detector width
ED: Ejection distance
In free-falling applications, or whenever the immediate activation of the ejection after an alarm is required, set ED=0.
Set ET at the minimum value that grant the correct removal of the contaminated material.
In applications at high trasnport speed, where the ejection activation time is not negligible, it is possible to anticipate its
activation through the parameter ERT.
THS-RB systems
The ejection signal is sent to the checkweigher that will manage the ejection itself.
In this case set EM=F and ED=0.