www.cegasa.com Page -10-
User Manual R10
–
First steps
–
•
Safety apparel that covers the whole body (long sleeves) shall be used.
Fireproof or flame retardant, with protection against chemicals and arc
flash.
•
The work shall be done from a solid, stable support
•
If a work table is used, it shall be insulated or covered with Insulating
matting.
•
No terminal with an electrical charge should be left uncovered. If, after
removing the connections, the terminals are exposed then they have to be
protected with the terminal covers supplied.
•
All tools shall be insulated and rated up to 1000V
•
Insulating gloves, at least class 0 (1000V), shall be worn until existing
voltages are cut to levels below 50V DC.
•
Operators shall not wear or carry any metal elements or devices.
•
The work area shall be free of obstacles.
•
If necessary, when there are exposed terminals nylon slings shall be used
instead of chains.
•
The operator shall wear a face shield or safety glasses to protect against
short-circuits
•
Occasionally, depending on the operation, there should be an OHS
assistant present.
•
This person should satisfy that stated in Annex IV of RD 614/2001
4 Assembly of the equipment
Caution
: Given that the modules are supplied with electrical charge levels necessary to
maintain the chemical properties of the batteries, the entire installation process shall
perform with the recommended protection equipment.
Each battery module and MCP are pre-wired, pre-set and factory tested. After receiving
and unpacking the system, the installer should find that each string contains:
-
An MCP module
-
Various eBick modules, these will be P or S depending on the system set-up.
-
A BUS termination resistor
-
S-BRIDGE CONNECTOR - Only for eBick-S set-ups connected in series
-
PROTECTIVE COVER - Only for eBick-P set-ups connected in parallel
-
One or more base frames with feet and wall or floor mounting plate/s
-
A set of fastening plates for between modules, base frame and MCP (with
fasteners)
-
A set of KIT communications and power extenders (*)
(*) Should the project have more than 4 modules, these have to be distributed in several
columns. The wiring between columns will be done using these extension cables.