DUAL INPUT INVERTER 

Commercial Power as default source

AC BACKUP IN A DC ENVIRONMENT 

Leverage your existing DC infrastructure

ONE STOP SHOP  

Wide output power range

HARSHEST AC INPUT CONDITIONS 

Without compromising the quality of the AC output

BEYOND THE INVERTER  

THE NEW GENERATION OF POWER CONVERTERS

www.cet-power.com

TSI NOVA - 230VAC

User Manual V7.3

Содержание TSI NOVA

Страница 1: ...E T S a Rue du Charbonnage 12 B 4020 Wandre Belgium www cet power com info cet power com DUAL INPUT INVERTER Commercial Power as default source AC BACKUP IN A DC ENVIRONMENT Leverage your existing DC...

Страница 2: ...blocks 13 5 1 Inverter 13 5 2 Sub rack 13 5 3 Monitor unit T1S T2S 14 6 Accessories 15 6 1 Cabinet 15 6 2 Manual by pass 15 6 3 AC distribution unit 16 6 3 1 Distribution Rack 16 7 Monitoring accessor...

Страница 3: ...ble DC Input 48VDC X1 29 10 4 8 Signalling 29 11 Interface 31 11 1 Inverter module 31 11 2 T1S 32 11 2 1 T1S alarm 32 11 3 T2S 32 12 System set up 33 12 1 Communication settings 33 12 2 Menu access 34...

Страница 4: ...45 18 1 Trouble Shooting 45 19 Maintenance 46 19 1 Access T2S with lap top 46 19 2 Manual check 46 19 3 Optional 46 19 4 Manual by pass 46 20 Defective modules 47 21 Appendix 48 21 1 Cabinet foot pri...

Страница 5: ...n Release date DD MM YYYY Modified page number Modifications 7 0 10 12 2012 First release of the Manual 7 1 to 7 2 18 10 2013 Amendment and correction 7 3 24 10 2016 Amendment and correction 5 TSI Nov...

Страница 6: ...e AC backup solution that unlike most used UPS s Maximizes the operator s applications uptime Operates with lowest OPEX Provides best protection to disturbances Optimizes footprint Our systems are Mod...

Страница 7: ...Electro Static Discharge MET Main Earth Terminal MBP Manual By pass TCP IP Transmission Control Protocol Internet Protocol USB Universal Serial Bus PE Protective Earth N Neutral PCB Printed Circuit Bo...

Страница 8: ...experience related to electrical maintenance Please follow the procedures contained in this Manual and note all the DANGER WARNING AND NOTICE marks contained in this Manual Warning labels must not be...

Страница 9: ...nds an external protection must be provided so that the short circuit protection operates within 5 seconds Default setting is 60 seconds The system is designed for installation within an IP20 or IP21...

Страница 10: ...g operation Contact may result in fatal injury 3 5 Replacement and Dismantling ESD Strap must be worn when handling PCBs and open units CE T cannot be held responsible for disposal of the Inverter sys...

Страница 11: ...of the active source The BOOST functionality multiples the nominal current for a period of 20 ms max in the event of downstream failures The upstream breakers do not have to be oversized to prevent tr...

Страница 12: ...ns input AC is the primary source whilst DC works as backup The TSI is designed to operate on Mains on a permanent basis and to deliver output voltage conditioned with low THD The output sine wave is...

Страница 13: ...phase or three phase configurations The fan is equipped with an alarm and run time meter The fan is field replaceable 313 D x 104 5 W x 41 5 H 1 5 Kg 5 2 Sub rack The NOVA shelf shall be integrated in...

Страница 14: ...ors max 32 inverters in one bus The T1S provides Alarm monitoring 2 outgoing alarms 2 digital inputs Dip switch for local setting The T2S provides Alarm monitoring Recording of the latest 200 events F...

Страница 15: ...that create a by pass from mains input to output AC distribution Inverter modules are by passed and possible to remove without impacting the load When in by pass shelves and modules have no AC supply...

Страница 16: ...oltage test point Max current per AC DU is 20 A max current per output connector is 6 A applicable only up to 4 5 KVA A la Carte system pack Alarm for AC output breakers a inbuilt to each individual b...

Страница 17: ...isplay units and 1 TCP IP agent 7 1 1 Display Backlit 2 line dot matrix The display shows two values simultaneously 7 1 2 TCP IP Agent The TCP IP interface board is mounted on the CanDis shelf and is...

Страница 18: ...em The system comprises cabinet inverter sub rack inverter modules manual by pass monitor device T2S and AC output distribution The A la Carte is available as EPC Enhanced Power Conversion or REG Regu...

Страница 19: ...t modules from one phase are not mixed with modules from another phase The system is designed for installation in an IP20 or IP21 environment When installed in a dusty or humid environment appropriate...

Страница 20: ...terminations All cables shall be rated at min 90 deg C Electrical terminations shall be tightened to 3 Nm All connection screws are M4 x 12 mm DC Input Common per shelf observe polarity AC Input AC ou...

Страница 21: ...lightning surge suppression device in service Indoor sitesMin Class II Outdoor sites Min Class I Class II or combined Class I II 9 2 3 Terminations All terminations are clearly marked 9 2 4 Grounding...

Страница 22: ...per shelf Cable min Connector Torque Nova pack Single shelf 2p 10 A 3 x 1 5 mm2 M4 3 Nm Nova pack Double shelf 2p 20 A 3 x 2 5 mm2 230 VAC 2p 16 A 3 x 1 5 mm2 9 2 8 Signalling Relay characteristics S...

Страница 23: ...connected to any shelf The remote ON OFF requires changeover contacts one input opens as the other closes The status is not changed unless both transitions are detected Relay characteristics Remote O...

Страница 24: ...s way The internal bus is connected from the first shelf to the last shelf 9 2 11 Rear cover The rear cover provides IP 20 protection for the rear terminations when required The rear cover is snapped...

Страница 25: ...net on location 10 3 Fixing the cabinet to the floor The cabinet is fixed through the base of the cabinet Remove lowest front cover to gain access to the fixing holes Max screw diameter is 22 mm See H...

Страница 26: ...he cables Ground PE DC Input X1 AC Input X2 Alarm X3 X5 X6 AC Output X4 AC Output distribution X4 DC Input X1 AC input X2 Alarm X3 Digital in X5 Remote ON OFF X6 Bulk AC output X4 Manual by pass S2 S1...

Страница 27: ...lations Min 16 mm2 10 4 4 AC Input X2 The AC input is wired to a screw terminal Max cable area is 16 mm2 10 4 4 1 Single phase L N PE 10 4 4 2 Three phase NOTE The three phase input is 123 ABC RST pha...

Страница 28: ...Individual input Individual DC input per shelf and return Max 16 mm2 per connection terminal 10 4 6 Connection Table AC Input X2 The AC input supply breaker shall be 2p for single phase and min 3p for...

Страница 29: ...lug 1ph 3ph Fuse CB Min Cable mm2 Fuse CB Min Cable mm2 3 63 16 6 125 A 35 63 A Live Screw terminal 10 mm2 Common Cable lug M4 3 Nm torque 9 200 A 95 9 12 250 120 15 350 A 240 18 400 A 240 18 10 4 8...

Страница 30: ...helf The remote ON OFF requires changeover contacts one input opens as the other closes The status is not changed unless both transitions are detected Digital input characteristics Remote ON OFF Signa...

Страница 31: ...erly Blinking green orange alternatively Recovery mode after boost 10 In short circuit condition Permanent orange Starting mode Blinking orange Modules cannot start Check T2S Blinking red Recoverable...

Страница 32: ...cy No Redundancy Redundancy 11 2 1 T1S alarm Description Type 1 Redundancy plus one inverter lost by Major 2 TSI Bus defect Major 3 Incompatability parameter Major 4 Main source lost see configuration...

Страница 33: ...r CET_T2S inf installed on laptop Available for download at http www acbackuptsi com Username T322010000 Password No password required enter Read T2S manual for detailed setup 12 1 Communication setti...

Страница 34: ...eturn to previous menu 1 14 Page number selection 16 Clear log 17 Save log to a file 6 Module errors information 0 Return to preceding menu 1 32 detailed Modules errors 3 System actions selection 0 Re...

Страница 35: ...The handle only fixes the module to the shelf Use a screwdriver to release the handle latch Open the handle and pull the module out Replace with a new module or blanking unit 13 1 2 Inserting Check mo...

Страница 36: ...he FAN life is approximately 60 000 Sixty Thousand hours The inverter modules have fan runtime meters and fan failure alarm Fan failure can result from a failing fan or driver circuit 1 Unplug the mod...

Страница 37: ...ore tightening the Torx screws at front side of the module 12 Place the front cover and push gently make sure the front cover latch is locked properly 13 Insert the Nova module back in its slot in the...

Страница 38: ...rcuit breakers are normally factory installed How to add breakers 1 Insert the short connection cable 10 mm2 included in the breaker Line side and tighten Up to 40 A breaker use one connection cable 6...

Страница 39: ...g the MBP procedure depending on voltage network and output Inverter voltage setting To reduce the impact of an overload the inverter power and current will be reduced from 150 to nominal value The by...

Страница 40: ...s reach full operation and have synchronized 30 60 seconds 4 Complete twist to OFF 15 2 3 Manual by pass 20kVA The manual by pass operates via three individual switches S2 S1 and S3 It creates a by pa...

Страница 41: ...dual switches S2 S1 and S3 It creates a by pass from the mains input to the output AC distribution Inverter modules are by passed allowing disconnection without impacting the load 15 3 1 1 Normal to B...

Страница 42: ...sure that all cables are strain relieved Make sure that all breakers comply with recommendations and local regulations Make sure that DC polarity complies with marking Re tighten all electrical termin...

Страница 43: ...will result in not all modules operating when running on DC and module failure when the AC input recovers from the fault condition Installation and commissioning must be done and conducted by trained...

Страница 44: ...to site conditions LVD load on AC AC threshold level Switch OFF ACin and check if system is working on DC Switch ON ACin and check if system correctly transferred load on AC Switch OFF system and sta...

Страница 45: ...DC Check AC input present and in range AC breakers Check DC input present and in range DC breakers Check the configuration and setting Check threshold level s No output power Check output breaker All...

Страница 46: ...compressed air Check module system load Check Correct inverter mapping DC group AC group Address Change configuration file to validate that system operates on both supply sources Check outgoing alarm...

Страница 47: ...y cet power com extranet Repair registering guidelines may be requested by email at repair cet power com The RMA number should be mentioned on all shipping documents related to the repair Be aware tha...

Страница 48: ...21 Appendix 21 1 Cabinet foot print layout 48 TSI Nova User manual v7 3 Appendix...

Страница 49: ...X3 7 6 5 4 3 2 1 9 8 3 2 1 X5 X6 2 3 1 L N PE PL12 N L PE L N PL5 N L PL3 N L PL4 N L PL3 PL5 2 3 1 L N PL12 PE PL5 N L PE L N PL3 L N PL4 PL4 N L X11 L L L L X12 N L L N X2 2 5 8x IEC SOCKET TSI AC O...

Страница 50: ...nr 18 Zoning Industriel TELECOMMUNICATIONS CONSTRUCTIONS ELECTRONIQUES Sheet Number Nr DATE MODIF CHECKED BY DRAW BY APPROVED BY APPROVED BY DRAWING NUMBER PART DESCRIPTION 05 11 08 M REGNIER J BOZZER...

Страница 51: ...21 4 Mains connection single phase TN S 400 230VAC L1 L2 L3 N PE PEN L3 L2 L1 TN C 400 230VAC PE L3 L2 L1 TN C S 400 230VAC N PEN TT 400 230VAC L1 L2 L3 N 51 TSI Nova User manual v7 3 Appendix...

Страница 52: ...21 5 Mains connection three phases PE N L3 L2 L1 TN S 400 230VAC TN C 400 230VAC L1 L2 L3 PEN N L3 L2 L1 TT 400 230VAC TN C S 400 230VAC L1 L2 L3 N PE PEN 52 TSI Nova User manual v7 3 Appendix...

Страница 53: ......