2.4. MBP Wiring
Both solutions (rotary by-pass or separate switches) need to have auxiliary contacts that need to be wired to the
monitoring unit as described below and as shown on the drawing present in annexe
Aux 3 (from the by pass switch) : Provides an input to the controller indicating that the MBP is engaged
Aux 1 (From AC input switch) and Aux 2 (from the by pass SWITCH):
•
Switch OFF the Flexa modules once the MBP is engaged.
•
Allow the Flexa modules to switch ON when the MBP placed in the INTERIM position.
Note:
The parameter “Out voltage consign” set by default to 230 Vac shall be adjusted according nominal AC input voltage.
This will limit the inrush current when operating on Smart By pass and Manual By pass.
54
– Flexa 200 - 400/400 – User Manual – v1.0