20
REVEX
1PH 280A
User’s manual
Wiring instructions
The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for
this reason in accord to the fundamental practices rules is opportune take some precautions:
•
The coil contactor, the relays and other inductive loads must be equipped with opportune RC filter.
• Use shielded bipolar cables for all the input and output signals.
• The signal cables must not be near and parallel to the power cables.
• Local regulations regarding electrical installation should be rigidly observed.
Use 75°C copper (CU) conductor only, wire ranges (AWG), wire terminal type (ZMVV), terminal tightening
torque in the table below.
8.1 Removing the cover
8
8.2 Power cable torque (suggested)
Current
Connector type
Torque
Lb-in (N-m)
Wire
Range
AWG / kcmil
Wire
Terminal
280A (S10)
Terminal Block M8
265 (30.0)
1
3/0
Copper wire
Compact (Solid) Stranded
8.3 Power cable dimensions (suggested)
Current
Supply
Load
Cable
Screw
Cable
Screw
mm²
AWG
M
mm²
AWG
M
280A (S10)
120
4/0
M8
120
4/0
M8
8.4 Cable dimensions (suggested) of Earth and of the Command Terminals
Current
Earth
Command Terminals
Cable
Screw
Cable
mm²
AWG
M
mm²
AWG
280A
25
4
M6
0,50
18