background image

to connect the power supply. The product label 

must not be removed as it contains important 

information regarding the product.

All alarms to be connected in the house should 

be put into ‘Learn Mode’ by sliding the switch on 

the back of the alarm to the ‘Learn Mode’ position.

Please note: The learn switch placed on the back 

of the alarm can only be in learn position when 

the alarm is disassembled from the power supply 

unit. The learn switch will automatically switch to 

normal position when the alarm head is fitted to 

the power supply.

The red LED will light up to indicate that ‘Learn 

Mode’ has been selected. 

Do not remove the battery during ‘Learn Mode’ as 

this will interrupt the learn process.

Press and hold  the test button at one alarm only, 

until it beeps and the LED flashes. This alarm will 

become the master and will start sending out a 

specific house code to the other alarms.

As  the  other  alarms  receive  the  specific  house 

code, they will also flash the LED light.

When all alarms flash the red LED, they are 

connected and can be switched out of ‘Learn 

Mode’ and installed.

2.

 THE BEST AREAS TO INSTALL THE SMOKE 

ALARM:

• Note the local country regulations regarding 

installation. 

• Note the local regulations about information 

to your insurance company regarding installed 

smoke alarms.

• Install an alarm between possible fire sources 

and bedrooms as a minimum.

• Install alarms on each floor of the house, in 

hallways and stairways. 

• Alarms in each room such as bedrooms and 

living rooms.

Additional alarms increase the security. 

3. 

AREAS WHERE NOT TO INSTALL SMOKE

ALARMS:

• In dusty rooms
• At the top of a high pointed ceiling, in ceiling 

corners, and within 50cm of a wall.

• In rooms where temperature goes outside the 

range +4

o

 to 38°Cor above 90% relative humidity 

not condensing.

• In kitchens, garages, laundries, or too close to 

fireplaces; areas where either dampness, gases 

or smoke could occur.

Place the alarm where it is reachable in order to 

test the alarm and for maintenance.

4.

 PLACEMENT:

The smoke alarm is designed to be installed on 

a ceiling.

With a minimum of one smoke alarm per floor and 

a maximum distance between smoke alarms of 

10 meters.
For ceiling installation:

The smoke alarm should be a minimum of 50cm 

from the wall. 

For cathedral or peak ceiling: 

Mains powered smoke alarm device

Commercial reference: 2201-003

Developed by CAVIUS

The smoke alarm is designed for private homes.

PLEASE READ THE USER GUIDE 

CAREFULLY BEFORE INSTALLATION AND 

RETAIN FOR FUTURE USE.

TECHNICAL INFORMATION

The smoke alarm is powered by mains power 

(110-230V AC), with a lithium back-up battery 

CR2. Please note that you should only use batteries 

from one of the following suppliers: DURACELL 

or HUIDERUI. 

It can be RF interlinked with other 2201 alarms, 

and with other CAVIUS Wireless Family alarms.

The maximum number of alarms that can be inter-

linked within a house group are 32. 

Please note: These must be alarms from the CAVIUS 

 

The distance between interlinked alarms depends 

on the house layout and they should always be 

tested after installation. It is not advised to install 

alarms with a separation of more than 10m.

Diameter: 97mm. Height: 41mm (without mount-

ing base) 52mm (with mounting base).

Interlinked by RF: 868 MHz

Complies to standards: EN14604:2005 + AC:2008, 

EN300-220, EN50130-4:2011, EN60065. 

EN60950-1, RoHs, Reach. 

1.

 

HOW TO SET UP AND CONNECT ALARMS: 

Start by pulling out the battery isolation 

strip in the battery compartment 

as shown.

Please note: RF connection is done with the 

device powered with battery only. You do not have 

UK

CHAMBER

FILTER

OPTIONAL HOLE 

FOR LAMP WIRE 

TEST BUTTON

SIREN

RED & GREEN LED

ISOLATION 

STRIP

DO NOT 

REMOVE THE 

PRODUCT LABEL

1

NORMAL MODE

2

LEARN MODE

Minimum

1

1

2

Minimum 50cm 

from wall

Wall

Ceiling

Peak ceiling

Minimum 50cm 

from peak

Содержание 2201-003

Страница 1: ...garages laundries or too close to fireplaces areas where either dampness gases or smoke could occur Place the alarm where it is reachable in order to test the alarm and for maintenance 4 PLACEMENT The smoke alarm is designed to be installed on a ceiling With a minimum of one smoke alarm per floor and a maximum distance between smoke alarms of 10 meters For ceiling installation The smoke alarm shou...

Страница 2: ...d OFF Remove the plastic cover to access to the power supply connector Pass the lamp wire through the smoke alarm 5 INSTALLING THE SMOKE ALARM NOTE THIS ALARM NEEDS TO BE INSTALLED BY A PROFESSIONAL MAKE SURE ELECTRICITY IS SWITCHED OFF BEFORE STARTING THE INSTALLATION CAUTION LIVE NEUTRAL AND EARTH MUST BE CORRECTLY INSTALLEDAND NOT MIXED UP NOTE The alarm is delivered in the packaging with a dus...

Страница 3: ...d 8 ALARM MODE When the smoke is detected the smoke alarm will go into Alarm Mode It will sound the alarm signal and the red LED will flash The smoke alarm will also transmit the alarm signal to the other connected alarms which will also sound the alarm signal after a short delay The CAVIUS Wireless Family have two different alarm signals Alarm signal 1 is life threatening alarms like a smoke alar...

Страница 4: ...the battery respecting the polarities Attach the alarm on power supply by twisting clockwise until it clicks and test the alarm 14 OTHER INFORMATION Do not paint the alarm Disposal For battery and product please dispose properly at the end of life This is electronic waste which should be recycled WARNING Please remove dust cover after installation Smoke will not be able to reach the chamber while ...

Отзывы: