Quick Start Guide

Safety Systems | Safe-D-Stop

1. Wire Your Machine Control Unit (MCU)

The MCU terminals and pin numbering relative to the OCU buttons are identified 
in the system configuration drawing provided with your system. 

1.

In almost all cases the implementation of an appropriate main line contactor 
power circuit is required using K18 and K19 to maintain the Machine power 
and possibly K20 to reset the Machine, although this may be a local reset.

2.

Connect power and ground (per system specification) to J1 via a local 
disconnect switch. 

3.

Connect the correct antennas to the antenna connectors.

4.

Check the wiring and turn on the MCU power, the MCU LEDs, two power 
green, Heartbeat flashing red and status amber, the relays K18 and K19 will 
energize if all is OK. 

2. Charge or Install the Batteries

Rechargeable OCUs have tamper proof 
screws on the battery cover. Disposable 
battery (AA type) OCUs have cross head 
screws on the battery cover.

3. Turn on the Operator Control Unit (OCU)

1.

Press the ON button, this will 
wake the OCU from sleep to 
a fully tested PASSIVE 

non-

transmitting mode.

2.

You will see all LEDs flash 
briefly and the Haptic buzz to 
confirm they are all working.

3.

The center Status and Right-
hand LEDs 1 & 2 will then 
illuminate

ON

2nd

1st

4. Move to Active Mode

NB: For 2.4GHz Systems OCUs must have completed the Association process with its 
target MCU (this only needs to be done once, see the user manual)

From Passive Mode the OCU can be moved into an Active mode;

1.

Press the Stop Switch and then press the On switch within 3 seconds.

2.

The Status E-Stop LED will now flash showing it is transmitting.

3.

At this point the OCU is active, and the target machine will be under direct control.

Nimble: 9M60-9061-A002-EN | May 2022