Setting
Value
Active Range
Global
Mode Select
Output on High
Mode Settings > Active Time
1
Disabled
Mode Settings > Start Level
325 °F
Mode Settings > Stop Level
200 °F
1
Active time is disabled because the fan needs to stay on indefinitely or until 200 °F is reached.
Relevant Settings (Switched Outputs)
Setting
Value
Switched Output X
Auxiliary Sensor X (choose based on which Auxiliary Sensor is being used)
The following chart shows the connection between engine temperature and time. At approximately 10 minutes
run time, the temperature rises above the 325 °F start threshold and the fan turns on. The fan continues to run
as the temperature declines. When the temperature falls below the 200 °F stop threshold, the fan turns off.
5.5.7 Custom Sender Tables
Custom Sender Tables are created using the RapidCore Configurator Software when using a sensor that is not
supported by Cattron. The Configurator Software has the ability to create these custom tables, allowing the
controller to properly read the sensor data.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...