DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
38
9M02-9249-A001-EN
Revision A
Warning Name
Enabled Condition(s)
Description
Low Oil Pressure
Switched input set to "Oil Pres.
Warn" function. See the
switched input is active during the
Run Mode.
Low oil pressure warning.
4.7
Failures
Failures are conditions that cause the controller to shut down to prevent damage to the engine or generator.
These get enabled/disabled when you enable/disable various settings in the controller.
Notable failures are given in the following table.
Failure Name
Enabled Condition(s)
Description
ECM
Communication
Failure
Enabled if loss of ECM
communication is enabled. See
feature.
If the controller has not received messages from
the ECM for 6 seconds.
Exception*
Always enabled.
Occurs when there is an issue from which the
controller cannot recover. For example, EMI can
cause the microcontroller to enter a bad state, or
a software bug could cause the code to hang
while triggering the watchdog. In these cases,
the controller will reset and enter the failure state.
*The name is configurable so it may not match
what is shown here.
Failure To Stop
Disabled when
(Energize to Stop) is set to 0
seconds; otherwise, it is enabled. If
used, ETS On Duration should be
set to at least 2 to 3 seconds;
otherwise, this failure may occur
on a normal shutdown.
After ETS countdown is finished, if the speed
was greater than 50 RPM (600 RPM for
TG350/TG410 firmware 1.88 and above) for the
previous 2 seconds, then the controller triggers
this failure.
Load Imbalance
AC Current feature.
Generator load imbalance. Excessive AC current
on one or more of the three phases.
Low Air Pressure
Switched input set to
“Air Pres.
Fail
switched input is active during
starting.
Application specific.
Low Coolant Lvl
Switched input set to
“Cool. Lvl
Fail
switched input is active.
Low Coolant Level.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...