use of a switched input.
The following settings must be set in order for this feature to function.
•
Switched I/O > Switched In A/B/C/D/E > Function > RPM Switch (Primary RPM / 60 Hz - Secondary
RPM / 50 Hz Select). The switched input is only monitored before a start signal has been received. Once
a start signal has been received, changing the status of the switched input will have no effect
•
AC Monitor > Genset Freq. > Freq. Source > Auto Selection
•
Sensors > Engine Speed > RPM Switch > Primary (Primary RPM / 60 Hz)
•
Sensors > Engine Speed > RPM Switch > Secondary (Secondary RPM / 50 Hz)
The following table shows the relationship between the switched input status and the RPM / Frequency.
Switched Input
Speed / Frequency
Inactive
Primary RPM / 60 Hz
Active
Secondary RPM / 50 Hz
CAUTION
IF ENABLED, THE J1939 TSC1 PGN WILL BE BROADCASTED ACCORDING TO THE SELECTED
SPEED. OTHERWISE, ONLY THE WARNING AND FAILURE SETPOINTS ARE AFFECTED BY
THIS FUNCTION.
ATTENTION
S'IL EST ACTIVE, LE PGN J1939 TSC1 SERA DIFFUSE SELON LA VITESSE SELECTIONNEE.
DANS LE CAS CONTRAIRE, SEULS LES POINTS DE CONSIGNE D'AVERTISSEMENT ET DE
DEFAILLANCE SONT AFFECTES PAR CETTE FONCTION.
5.7.3 Generator Current
The following settings are used to configure the controller
’s responses to current measurements.
AC Monitor > Genset Current
Name
Range
Default
Description
Current Source
Enable
Disable
Enable
Enables or disables current metering.
Turns Ratio
5 ~ 5000 A : 5 A
in 5 A increments
100 A : 5 A
The turns ratio of the current transformers.
Scaling Factor
0.500 ~ 1.250
in 0.001 increments
1.000
Scaling factor at which the current is read
into the controller. See below for more
information.
Rated Amps
5 ~ 5000 A
in 1 A increments
100 A
Maximum current draw that the generator
can provide when operating under normal
running conditions.
!
!
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...