CANplus CP750-E
Control Panel Operation Manual
*Patent Pending
28
9M02-1000-A501-EN
Revision B
6.4.4 Configuring Start and Stop Delays
In situations where start or stop conditions may be met briefly, yet repeated start/stop cycles of the engine need
be avoided, two settings allow a delay to be added before a specific input condition is recognized. An example of
such use is where a float switch is installed in choppy water. The float switch may repeatedly open and close
based on the water’s surface waves. Rather than repeated engine start and stop cycles, it is better to wait for the
float switch to be continuously closed for a specified duration before the start or stop event is declared.
The Start and Stop Delays can be configured by going to the
Autostart
→
Behavior
→
Start Delay or Stop Delay
menu.
6.4.5 Ramp Profile
The Auto ramp profile allows the use of configurable warm up and cool down profiles to help protect engines and
other assets such as plumbing, or to ensure proper ramp up and down of pressure or flow. An example is shown
below.