6.4.1 Configuring Operation
Configuring Autostart begins with selecting the desired behavior. The two choices are as follows:
1.
High to low, examples:
•
High water level to low water level
•
High pressure to low pressure
•
High temperature to low temperature
2.
Low to high, examples:
•
Low water level to high water level
•
Low pressure to high pressure
•
Low temperature to high temperature
6.4.2 Configuring Start and Stop Events
The next step is to define the start and stop events. The choices are as follows:
•
Single switch
•
Cycle Run
–
Start upon entering Autostart modes
–
Stops after x minutes
–
Restarts after y minutes
•
2-State, Single Switch
–
Manually started and stopped
–
Switched input toggles between idle and Intermediate RPM
•
Remote Control
–
Start and stop via switch
–
Throttle up and down via two other switches
–
Single start/stop
•
Dual switch
–
Start and stop via dual (high and low) switches
•
Transducer
–
Start and stop via transducer level
•
Transducer with backup switches
–
Start and stop via transducer level
–
Switches as backup start and stop if there is a transducer failure
•
Scheduler
•
Timed run
–
Manually started
–
Automatically stopped by countdown timer
–
Can maintain a level while running