Icons and text indicators
ZS Sensor
CARRIER CORPORATION ©2020
Applications Guide
All rights reserved
18
4
Under
Show when active as
, check
Alarm
to display
on the Home screen and any other selected screen.
5
Optional: To display details about the active alarm, check a
Show on
screen to display the
Active Text
and
Rnet tag.
NOTE
When active, alarm information will automatically display first on the assigned screen, regardless of
the display order you define.
In the example below, the Rnet tag for
High Zone Temp Alarm (1025)
is set to show on the
Information screen
.
Because
Alarm
is checked,
will display on the Home screen. When the user presses the button, the
Information screen will show the icon, the Rnet Tag
1025
, and the Active Text
Hi Zone
.
Maintenance icon
The indicates a maintenance condition versus an alarm condition.
1
From the
Sys Out
microblock menu, add a
BACnet Binary Value Status
microblock.
2
On the Property Editor's
Rnet
tab, check
Enable Rnet
.
3
Select a pre-defined maintenance condition (1XXX) from the
Rnet Tag
drop-down list.