Relative Humidity sensors
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
57
To wire and mount the Duct RH sensor
1
Drill a .75 inch (1.9 cm) diameter hole in the duct where the sensor is to be mounted.
2
Insert the stainless steel probe into the hole until the foam contacts the duct, then attach the RH sensor
using the 2 self-tapping screws provided.
3
Remove the cover.
4
On the probe unit, remove the knockout's inner ring.
5
If you are not using a .5 inch (1.3 cm) NPT conduit fitting, remove the knockout's outer ring. Tap the ring in 1
or 2 locations with a screwdriver, then remove the ring.
6
Install your conduit connectors or watertight fittings.
7
Wire the unit for power. See
Typical power wiring diagrams for Duct RH and Outdoor RH sensors
(page 60).