Installing Heat Reclaim Ventilation
Power Connection Definition
1. Wiring Notice—Shut off Power Prior to Whatever Job.
• The machine must be connected to the ground according EN 60364.
• Circuit breaker capable of shutting power off the whole system shall be installed. Please make sure that earth
connection is available.
• A switch and fuse shall be available for every single power line. Circuit or creepage breaker shall be available
for whatever wiring job.
• Make sure that ground impedance does not exceed 100 ohms. When creepage breaker is available, ground
impeder can be used to accommodate impedance over 500 ohms.
• Power line, connection line, air switch shall be prepared by users.
• Power line model: YZW power line; size must meet local criteria. Must adopt the triple-core shielded wire
with sleeve, such as H05VV-F, H05RN-F, H07RN-F, which are approved by local authority. The size of
the conductor shall not less than 0.75mm2. While connecting the power line, make sure current-carrying
conductors become taut before earthing conductor, if the cord slips out of the cord anchorage.
• Fuse Spec: 15A.
• Power lines of different specs shall not be connected to the same terminal. Overheating will ensue in case of
loose terminal connection.
• Power lines of different specs shall not be connected to the same ground terminal. Protection will be impaired
in case of loose connection.
• Keep certain distance between power lines and other connection cables to prevent noise.
• For wiring method, refer to circuit diagram. Wiring notice: every cable shall be connected to its corresponding
terminal according to its unique polarity, and shall have its sign matched up with terminal sign.
2. Open and Close Electrical Cabinet
• Before opening the cabinet cover, make sure that power connections to unit components are shut off.
• Unscrew bolts fixing the cover and open the cabinet.
• Fix power line with clamp and make sure that earth connection is available. Connect control and signal lines
to corresponding terminal blocks.
• Please use shield wire as signal line.
• Upon completing wiring job, please mount the cabinet cover in good manner.
25
Содержание XCT7 40VH A-7G Series
Страница 29: ...21 Installing Heat Reclaim Ventilation Terminal A and B on Heat Reclaim Ventilation PCB CN501 Red Black Sensor...
Страница 36: ...The manufacturer reserves the right to change any product specifications without notice...
Страница 67: ...Il produttore si riserva il diritto di modificare qualsiasi specifica del prodotto senza preavviso...
Страница 98: ...Le fabricant se r serve le droit de modifier les sp cifications du produit sans pr avis...
Страница 129: ...Der Hersteller beh lt sich das Recht vor Produktspezifikationen ohne Vorank ndigung zu ndern...
Страница 160: ...El fabricante se reserva el derecho de cambiar cualesquiera especificaciones de producto sin previo aviso...
Страница 191: ...O fabricante reserva se o direito de alterar as especifica es do produto sem aviso pr vio...