Table 5 — Cooling Service Troubleshooting
PROBLEM
CAUSE
REMEDY
Compressor and Condenser Fan Will
Not Start.
Power failure.
Call power company.
Fuse blown or circuit breaker tripped.
Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Replace defective component.
Insufficient line voltage.
Determine cause and correct.
Incorrect or faulty wiring.
Check wiring diagram and rewire correctly.
Thermostat setting too high.
Lower thermostat setting below room temperature.
Compressor Will Not Start But
Condenser Fan Runs.
Faulty wiring or loose connections in
compressor circuit.
Check wiring and repair or replace. Tighten loose
connections.
Compressor motor burned out, seized, or
internal overload open.
Determine cause. Replace compressor.
Defective run/start capacitor, overload, start
relay.
Determine cause and replace defective component.
One leg of three-phase power dead.
Replace fuse or reset circuit breaker. Determine cause.
Compressor Cycles (other than
normally satisfying thermostat).
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, and recharge to to
values on nameplate.
Defective compressor.
Replace defective compressor.
Insufficient line voltage.
Determine cause and correct.
Blocked condenser.
Determine cause and correct.
Defective run/start capacitor, overload, or start
relay.
Determine cause and replace.
Defective thermostat.
Replace thermostat.
Faulty condenser-fan motor or capacitor.
Replace defective fan motor or capacitor.
Restriction in refrigerant system.
Locate restriction and remove.
Compressor Operates Continuously.
Dirty air filter.
Replace air filter.
Unit undersized for load.
Decrease load or replace with larger unit.
Thermostat set too low.
Reset thermostat.
Low refrigerant charge.
Locate leak; repair and recharge.
Leaking valves in compressor.
Replace compressor.
Air in system.
Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted.
Clean coil or remove restriction.
Excessive Head Pressure.
Dirty air filter.
Replace air filter.
Dirty condenser coil.
Clean condenser coil.
Refrigerant overcharged.
Recover excess refrigerant.
Faulty TXV valve.
1. Check TXV bulb mounting and secure tightly to suction
line and insulate.
2. Replace TXV valve and filter drier if stuck open or
closed.
Condenser air restricted or air short-cycling.
Determine cause and correct.
Head Pressure Too Low.
Low refrigerant charge.
Check for leaks; repair and recharge.
Compressor valves leaking.
Replace compressor.
Restriction in liquid tube.
Remove restriction.
Excessive Suction Pressure.
High head load.
Check for source and eliminate.
Compressor valves leaking.
Replace compressor.
Refrigerant overcharged.
Recover excess refrigerant.
Suction Pressure Too Low.
Dirty air filter.
Replace air filter.
Low refrigerant charge.
Check for refrigerant leaks; repair and recharge.
Faulty TXV valve.
1. Check TXV bulb mounting and secure tightly to suction
line and insulate.
2. Replace TXV valve and filter drier if stuck open or
closed.
Insufficient evaporator airflow.
Increase air quantity. Check filter and replace if
necessary. Check belt tension on blower.
Temperature too low in conditioned area.
Reset thermostat.
Outdoor ambient below 25°F.
Install low-ambient kit.
Evaporator Fan Will Not Shut Off.
Time off delay not finished.
Wait for 30-second off delay.
Compressor Makes Excessive Noise.
Compressor rotating in wrong direction.
Reverse the 3-phase power leads.
Содержание WeatherMaster Puron 48HC D17
Страница 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Страница 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Страница 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Страница 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Страница 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Страница 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Страница 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Страница 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Страница 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Страница 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Страница 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Страница 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Страница 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Страница 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Страница 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Страница 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Страница 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Страница 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Страница 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Страница 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Страница 97: ......