95
Table 61 —
CCN Configuration
EDT Low Alert Limit/Occ (SA.L.O)
If the space temperature is below the configurable occupied
evaporator discharge temperature (EDT) Low Alert Limit
(
SA.L.O
), then Alert 302 will be generated and cooling opera
-
tion will be stopped, but heating operation will continue. The
alert will automatically reset.
EDT High Alert Limit/Occ (SA.H.O)
If the space temperature is above the configurable occupied
EDT High Alert Limit (
SA.H.O
), then Alert 303 will be gener
-
ated and heating operation will be stopped, but cooling opera
-
tion will continue. The alert will automatically reset.
EDT Low Alert Limit/Unocc (SA.L.U)
If the space temperature is below the configurable unoccupied
EDT Low Alert Limit (
SA.L.U
), then Alert 302 will be gener
-
ated and cooling operation will be stopped, but heating opera
-
tion will continue. The alert will automatically reset.
EDT High Alert Limit/Unocc (SA.H.U)
If the space temperature is above the configurable unoccupied
EDT High Alert Limit (
SA.H.U
), then Alert 303 will be gener
-
ated and heating operation will be stopped, but cooling opera
-
tion will continue. The alert will automatically reset.
RAT Low Alert Limit/Occ (RA.L.O)
If the return-air temperature is below the configurable occu
-
pied RAT Low Alert Limit (
RA.L.O
), then Alert 304 will be
generated and internal routines will be modified. Unit opera
-
tion will continue, but VAV heating operation will be disabled.
The alert will automatically reset.
RAT High Alert Limit/Occ (RA.H.O)
If the return-air temperature is above the configurable occupied
RAT High Alert Limit (
RA.H.O
), then Alert 305 will be generated
and operation will continue. The alert will automatically reset.
RAT Low Alert Limit/Unocc (RA.L.U)
If the return-air temperature is below the configurable unoccu
-
pied RAT Low Alert Limit (
RA.L.U
), then Alert 304 will be
generated. Unit operation will continue, but VAV heating oper
-
ation will be disabled. The alert will automatically reset.
RAT High Alert Limit/Unocc (RA.H.U)
If the return-air temperature is above the configurable unoccu
-
pied RAT High Alert Limit (
RA.H.U
), then Alert 305 will be
generated. Operation will continue. The alert will automatical
-
ly reset.
OAT Low Alert Limit (OAT.L)
If the outside-air temperature measured by the OAT thermistor
is below the configurable OAT Low Alert Limit (
OAT.L
), then
Alert T316 will be generated.
OAT High Alert Limit (OAT.H)
If the outside-air temperature measured by the OAT thermistor
is above the configurable OAT High Alert Limit (
OAT.H
), then
Alert T317 will be generated.
RARH Low Alert Limit (R.RH.L)
If the unit is configured to use a return air relative humidity
sensor (
Configuration
UNIT
SENS
RRH.S
), and the
measured level is below the configurable RH Low Alert Limit
(
R.RH.L
), then Alert 308 will occur. The unit will continue to
run, and the alert will automatically reset.
RARH High Alert Limit (R.RH.H)
If the unit is configured to use a return air relative humidity
sensor (
Configuration
UNIT
SENS
RRH.S
), and the
measured level is above the configurable RARH High Alert
Limit (
R.RH.H
), then Alert 309 will occur. The unit will con
-
tinue to run, and the alert will automatically reset.
OARH Low Alert Limit (O.RH.L)
If the unit is configured to use an outdoor air relative humidity
sensor (
Configuration
ECON
ORH.S
) and the measured
level is below the configurable OARH Low Alert Limit
(
O.RH.L
), then economizer operation will be disabled. The
unit will continue to run, and the alert will automatically reset.
OARH High Alert Limit (O.RH.H)
If the unit is configured to use a return air relative humidity
sensor (
Configuration
ECON
ORH.S
) and the measured
level is above the configurable OARH High Alert Limit
(
O.RH.H
), then economizer operation will be disabled. The
unit will continue to run, and the alert will automatically reset.
Supply Duct Pressure Low Alert Limit (SP.L)
If the unit is a VAV unit with a supply duct pressure sensor and the
measured supply duct static pressure is below the configurable SP
Low Alert Limit (
DP.L
), then Alert 310 will occur. The unit will
continue to run, and the alert will automatically reset.
Supply Duct Pressure High Alert Limit (SP.H)
If the unit is a VAV unit with a supply duct pressure sensor and the
measured supply duct static pressure is above the configurable SP
High Alert Limit (
SP.H
), then Alert 311 will occur. The unit will
continue to run, and the alert will automatically reset.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
CCN
CCN CONFIGURATION
CCNA
CCN Address
1 to 239
CCNADD
1
CCNB
CCN Bus Number
0 to 239
CCNBUS
0
BAUD
CCN Baud Rate
1 to 5
CCNBAUDD
3
BROD
CCN BROADCST DEFINITIONS
TM.DT
CCN Time/Date Broadcast
Off/On
CCNBC
On
OAT.B
CCN OAT Broadcast
Off/On
OATBC
Off
ORH.B
CCN OARH Broadcast
Off/On
OARHBC
Off
OAQ.B
CCN OAQ Broadcast
Off/On
OAQBC
Off
G.S.B
Global Schedule Broadcst
Off/On
GSBC
Off
B.ACK
CCN Broadcast Ack’er
Off/On
CCNBCACK
Off
SC.OV
CCN SCHEDULES-OVERRIDES
SCH.N
Schedule Number
0 to 99
SCHEDNUM
1
HOL.T
Accept Global Holidays?
No/Yes
HOLIDAYT
No
O.T.L.
Override Time Limit
0 to 4
HRS
OTL
1
OV.EX
Timed Override Hours
0 to 4
HRS
OVR_EXT
0
SPT.O
SPT Override Enabled?
No/Yes
SPT_OVER
Yes
T58.O
T58 Override Enabled?
No/Yes
T58_OVER
Yes
GL.OV
Global Sched. Override?
No/Yes
GLBLOVER
No
Содержание WeatherExpert 48N2
Страница 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Страница 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Страница 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Страница 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Страница 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Страница 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Страница 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Страница 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Страница 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Страница 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Страница 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Страница 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Страница 168: ...168 Fig 47 Sensor and Ignition Position Fig 48 Combustion Blower Details SENSOR DETAILS IGNITION DETAILS ...
Страница 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...