Wiring sensors to the VVT Zone II's inputs
You can wire the following sensors to the VVT Zone II's inputs:
•
Alternate space temperature sensor
(page 20)
•
Supply Air Temperature sensor
(page 20)
•
Duct Air Temperature sensor
(page 21)
•
CO
2
sensor
(page 21)
•
Relative Humidity sensor
(page 23)
•
Remote occupancy contact sensor
(page 24)
NOTE
This document gives instructions for wiring the sensors to the VVT Zone II. For detailed installation
instructions, see the device's
Installation Guide
.
WARNING
Disconnect electrical power to the VVT Zone II before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.
CAUTION
•
Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring.
•
Do not abrade, cut, or nick the outer jacket of the cable.
•
Do not pull or draw cable with a force that may harm the physical or electrical properties.
•
Avoid splices in any control wiring.
Wiring specifications
Cable from sensor to controller:
If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length:
500 feet (152 meters)