background image

Installing the UPC Open 

 

 

 

UPC Open 

Carrier Proprietary and Confidential 

CARRIER CORPORATION ©2017   

Installation and Integration Guide 

 

All rights reserved 

 

 

 

Wiring specifications for BACnet MS/TP and ARC156 

  

Cable: 

22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire 

Maximum length: 

2000 feet (610 meters) 

 

 

WARNING

  Do not apply line voltage (mains voltage) to the controller's ports and terminals. 

 
 
 

 

To wire the controller to the BACnet network 

Pull the screw terminal connector from the controller's power terminals labeled 

Gnd 

and 

Hot

Check the communications wiring for shorts and grounds. 

Connect the communications wiring to the controller’s screw terminals labeled 

Net +

Net -

, and 

Shield

.  

NOTE  

Use the same polarity throughout the network segment. 

Set the communication type and baud rate. 

  

 

 

For...

 

 

 

Set DIP switches 1 and 2 

to...

 

 

DIP switch 3

 

 

Set DIP switch 4 

to...

 

 

Set DIP switches 5 through 8 to...

 

MS/TP (m) 

The appropriate baud 

rate. See the 

MS/TP 

Baud 

diagram on the 

controller. 

N/A 

On 

Off/Off/Off/Off 

ARC156 

N/A. Baud rate will be 

156 kbps regardless of 

the DIP switch settings. 

N/A 

Off 

N/A 

   

NOTE

  Use the same baud rate for all controllers on the network segment. 

 

For MS/TP, verify that the EIA-485 jumpers are set to EIA-485 and 2w. 

Wire the controllers on a BACnet MS/TP or BACnet ARC156 network segment in a daisy-chain configuration. 

If the UPC Open is at either end of a network segment, connect a BT485 to the UPC Open. 

Insert the power screw terminal connector into the UPC Open's power terminals. 

Verify communication with the network by viewing a Module Status report in the i-Vu® interface.  

 
 
 

 

Содержание UPC Open

Страница 1: ...In ns st ta al ll la at ti io on n a an nd d I In nt te eg gr ra at ti io on n G Gu ui id de e CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog...

Страница 2: ...ur local Carrier office Important changes are listed in Document revision history at the end of this document CARRIER CORPORATION 2017 All rights reserved throughout the world i Vu is a registered tra...

Страница 3: ...pecifications 8 ZS Sensor overview 9 SPT sensor overview 9 To wire the ZS or SPT sensor to the UPC Open 10 Wireless sensor overview 10 To install the Wireless Adapter for wireless sensors 11 To wire a...

Страница 4: ......

Страница 5: ...eral purpose protocol converter The UPC Open can convert proprietary equipment data into open protocol data enabling a stand alone single piece of equipment to reside on a BACnet network where it can...

Страница 6: ...CN port Port 2 5 pin port supports EIA 485 3 wire connection to a single Carrier CCN controller LON OC port 14 pin communication port supports the LonWorks Option Card future Rnet port The UPC Open on...

Страница 7: ...0HF Cycoloy plastic Overall dimensions A B 5 3 16 in 13 2 cm 4 1 8 in 10 5 cm Mounting hole dimensions C D E 4 7 8 in 12 4 cm 2 1 20 in 5 2 cm 3 16 in 5 cm Panel depth 2 in 5 1 cm Weight 44 lbs 2 kg B...

Страница 8: ...edges Isolate from high voltage or electrostatic discharge Ensure that you are properly grounded Screw the UPC Open into an enclosed panel using the mounting slots on the coverplate Leave about 2 in...

Страница 9: ...ress that is unique on the MS TP or ARCNET network You can address the UPC Open before or after you wire it for power 1 If the UPC Open has been wired for power pull the screw terminal connector from...

Страница 10: ...NOTE Use the same polarity throughout the network segment 4 Set the communication type and baud rate For Set DIP switches 1 and 2 to DIP switch 3 Set DIP switch 4 to Set DIP switches 5 through 8 to MS...

Страница 11: ...r application which consists of 2 or 3 chillers configured for Lead Lag with a potential third chiller as a standby chiller In this application wire the CCN network between the UPC Open and chillers i...

Страница 12: ...nicating on the CCN Port NOTE If the CCN target address differs from what the UPC Open is configured for default 0 1 then only the transmit LED flashes about 1 time per second Wiring devices to the UP...

Страница 13: ...nsors ZS Standard ZS Plus ZS Pro NOTES A control program can use no more than 5 ZS Sensors so you must use 2 control programs if your Rnet network has 10 sensors The ZS CO2 model uses 190 mA during sa...

Страница 14: ...ommends that you use the following Rnet wiring scheme Connect this wire To this terminal Red Black White Green 12V Rnet Rnet Gnd Wireless sensor overview The Carrier wireless sensors designed for zone...

Страница 15: ...mains voltage to the Wireless Adapter To wire power and mount the Wireless Adapter NOTES The Wireless Adapter requires a 24 Vac or 24 Vdc power supply It is not powered by the Rnet If the Wireless Ad...

Страница 16: ...apter 7 Apply power to the external power supply 8 Verify that the LED on top of the Wireless Adapter is blinking See LED below 9 Turn on the controller s power LED The blue LED on the top of the Wire...

Страница 17: ...4 conductor Rnet cable and follow the instructions below For complete Equipment Touch installation instructions including wiring diagrams see the Equipment Touch Installation and Setup Guide 1 Turn of...

Страница 18: ...er s AC power ground could damage the USB Link and the controller If you are not sure of the wiring polarity use a USB isolator between the computer and the USB Link Purchase a USB isolator online fro...

Страница 19: ...Vu Control System page 15 to load your control program and graphic into the controller To install the UPC Open into an i Vu Control System You must complete the following procedures to successfully i...

Страница 20: ...hysical points by selecting the controller in the navigation tree and going to Properties page I O Points tab Enter your channel numbers under Num using your wire list Enter your expander address unde...

Страница 21: ...pplication the maximum number of UPC Open controllers allowed on the CCN bus is 3 CCN Alarm Acknowledger The UPC Open defaults as the CCN Acknowledger In a Multiple Chiller Application you must config...

Страница 22: ...tches are not replaceable but they will reset themselves if the condition that caused the fault returns to normal Rx Lights when the controller receives data from the network segment there is an Rx LE...

Страница 23: ...alternating with Run LED Ten second recovery period after brownout 14 flashes per second 14 flashes per second alternating with Run LED Brownout On On Failure Try the following solutions Turn the UPC...

Страница 24: ...fault configuration settings 1 Turn off the UPC Open s power switch 2 Put the Factory Defaults jumper on 3 Turn on the UPC Open s power switch 4 Remove the Factory Defaults jumper To replace the UPC O...

Страница 25: ...anual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correc...

Страница 26: ...Field Assistant and the i Vu interface on the Properties page Network Points tab The following example involves outside air temperature System Heat Cool Demand Level behaves similarly except that thei...

Страница 27: ...Device Address Binding allows the UPC Open to receive data from other Open controllers when they are connected by a network You must configure this method Currently the UPC Open allows Device Address...

Страница 28: ...ss Adapter for Wireless sensors To wire an Equipment Touch to the UPC Open New topics C D Wiring devices to the UPC Open s Rnet port Added Wireless Adapter for wireless sensors and Equipment Touch C D...

Страница 29: ......

Страница 30: ...CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 468 01 6 1 2017...

Отзывы: