Troubleshooting
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
63
5
Anything other than
No Fault Detected
indicates an error. See the table below to determine the error and
possible actions to take.
Reliability
description
Possible error
Verify that...
Communication
Failure
•
Expander is not connected to the
controller.
•
The expander has no power.
•
The controller is offline.
•
The expander is connected to the
controller's I/O bus edge connector or
wired to the I/O Bus port.
•
The expander has power.
Configuration
Error
•
The microblock's
I/O Type
and
Sensor/Actuator Type
are not
compatible.
•
The
I/O Type
and
Sensor/Actuator Type
combination is valid for the I/O number
and microblock type.
•
The output's DIP switch setting does
not match the connected device.
•
The DIP switch setting is appropriate for
the output and microblock type.
•
Invalid expander address or I/O
number.
•
The expander is present and functional at
the address shown in the i-Vu® interface
and that I/O number is valid.
Over Range
•
Input exceeds the
Min/Max
limits.
•
The input is within the
Min/Max
limits.
No Output
•
Output's
Hand-Auto-Off
switch is in
Hand
or
Off
position.
•
The expander's
Hand-Auto-Off
switch is in
the
Auto
position.
No Sensor
•
No device is attached to the output.
•
The device is present and functioning.
Shorted Loop
•
Internal voltage feedback does not
correspond with commanded value.
•
The load on the output is within the valid
range.
•
A voltage/current source has not been
connected to an output.
Open Loop
•
Internal current feedback does not
correspond with commanded value.
•
The load on the output is within the valid
range.
•
A voltage/current source has not been
connected to an output.
Unreliable Other
•
Feedback from the expander does not
correspond with commanded value (for
example, the output relay is not in
commanded state).
•
Expander may be faulty. Contact
Technical Support.
To get a Device Log
If Carrier Control Systems Support instructs you to get the controller's Device Log containing diagnostic
information for troubleshooting:
1
Select the TV-UCXP683T-V in the i-Vu® navigation tree.
2
On the
Properties
page, click
Device Log
.
NOTE
You can click
Device Log Archive
to download a file containing multiple Device Logs to your computer. This
also contains any network packet captures that have been run from the
Network Diagnostics - Packet Captures
(page 43) driver page.
Содержание TruVu UCXP683T-V
Страница 75: ......
Страница 76: ...Carrier 2021 Catalog No 11 808 850 01 12 3 2021...