To adjust input and output properties
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
29
Input values
Input
I/O Type
Sensor/Actuator Type
Min/Max
Analog (BAI)
0-5 Vdc
0
–
5 Volt
Linear Full Range
Engineering values associated with 0
Vdc (Min) and 5 Vdc (Max)
1
No Translation
N/A. The input microblock's value will be
the raw voltage of the input.
0-10 Vdc
0
–
10 Volt
Linear Full Range
Engineering values associated with 0
Vdc (Min) and 10 Vdc (Max)
1
No Translation
N/A. The input microblock's value will be
the raw voltage of the input.
2-10 Vdc
0
–
10 Volt
Linear w/Offset,
2
–
10 Volts
Engineering values associated with 2
Vdc (Min) and 10 Vdc (Max)
1
Thermistor
Thermistor
Select your Thermistor type or
set up and select a
Non-Linear,
Custom Table
2
N/A
Pulse to Analog (BPTA)
3
Pulse Counter
Counter Input
N/A
N/A
Binary (BBI)
Dry Contact
Dry Contact
N/A
N/A
1
The sensor reads a value and sends a corresponding signal (Volts) to the TV-UCXP683T-V's physical input. The
Analog Input microblock uses the Min and Max values to linearly translate the signal into the engineering value
used in subsequent control logic.
2
You can set up a custom translation table on the driver's
Custom Translation Tables pages in the i-Vu®
interface.
3
The control program must have one Pulse to Analog Input microblock for each pulse counting input.