![Carrier TruVu UC683T Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/carrier/truvu-uc683t/truvu-uc683t_installation-and-startup-manual_2563916063.webp)
Troubleshooting
TruVu™ UC683T
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
59
To configure custom Prog LED
You can customize the
Prog
LED for site-specific purposes by configuring the BACnet Analog Output (BAO)
microblock.
Open your control program in the Snap interface, select the AO microblock for the LED, and use the following
settings:
Status/Attribute
Microblock
type
Expander number :
Channel number
I/O type
Description
LED
BAO
0:61
Special
•
<=0 Normal
•
>15 On
The number of blinks equals the
Present Value.
The pulse pattern repeats after a
2-second delay
LED will blink the number of
times given in the BAO with ON
pulse 0.5 seconds and OFF pulse
0.5 seconds.
To get a Module Status report
A Module Status report provides information about the controller and verifies proper network communication with
the controller. You can get this report:
•
In the i-Vu® application
—
Right-click the controller on the navigation tree, then select
Module Status
.
•
In the Field Assistant application
—
Right-click the controller in the navigation tree and select
Module Status
.
•
On the controller setup
ModStat
tab
—
See
To set up the controller through the Service Port
(page 46).
See
Module Status field descriptions
(page 66) in the Appendix.