Appendix A: Module Status field descriptions
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
81
Field
Description
Date/Time
Date and time the Modstat was run
CM
The controller's rotary switch address (MAC address)
Model Name
Identifies the Product Type
Device Instance
A unique ID assigned to the controller
Driver built
When the driver was built
Downloaded by
When and where the last download was performed
Application Software Version
The name of the first control program that is downloaded
Data Partition Version
Data Partition identifies the clipping used when the product was
manufactured.
NOTE
This field will say
None
except for a Carrier product from the factory. If a
Carrier product is subsequently downloaded in the field, then this field will say
None
.
# PRGs initialized
# PRGs running
If applicable, the number of control programs that were downloaded vs. the
number that are running. If these numbers are not the same, the controller
has a problem such as lack of memory.
Driver version
The name, version, and date of the driver, as well as all the bundles and
versions.
Reset Counters:
The number of times each of the following events have occurred since the last
time the controller was commanded to clear the reset counters.
See
NOTE
below this table.
Power failures
Interruption of incoming power
Commanded boots
Includes commands issued from the i-Vu® interface such as the zap manual
command, plus commands issued during a memory download.
System errors
Error in the controller's firmware or hardware
S/W Watchdog
timeouts
Watchdog is firmware that monitors the application firmware for normal
operation. If the watchdog firmware detects a problem, it restarts the
application firmware.
H/W Watchdog
timeouts
H/W Watchdog will restart the controller if it detects a severe problem with the
controller's operating system
System status
Gives the current status of the controller's operation. See
LEDs
(page 70) for
all possible conditions.
Network status
Gives the current status of the controller's networks. See
LEDs
(page 70) for
all possible conditions.
System error message history
High-severity errors since the last memory download. Shows the most recent
10 messages.
See
NOTE
below this table.
Appendix A: Module Status field descriptions