Adjusting the TV-MPCXP1628-NR driver properties
TruVu™ MPC Controller (
part no. TV-MPCXP1628-NR)
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
48
Device
The
Device
page provides the following information plus the items described in the table below:
•
BACnet device object properties for the TV-MPCXP1628-NR
•
The character sets supported by this device for BACnet communication
Configuration
BACnet System Status
The current state of the controller:
Operational
Download in Progress
Download Required
Backup in Progress
Non-Operational
The following fields refer to all networks over which the TV-MPCXP1628-NR communicates.
APDU Timeout
How many milliseconds the device will wait before resending a message if no
response is received.
APDU Segment Timeout
How many milliseconds the device will wait before resending a message segment
if no response is received.
Number of APDU Retries
The number of times the device will resend a message.
Controller Clock
Time Broadcaster will
synchronize time every ____
If you have third-party BACnet devices on one of the router's networks, you can
have the router send a BACnet time sync to those devices at the interval you
define in this field.
Time Synchronization
Recipients
To define third-party BACnet devices as Time Synchronization Recipients:
1
Click
Add
.
2
Select
Device ID
or
Address
in the
Recipient Type
field.
3
Enter the
Device ID
or
Address
information.
4
Click
Accept
.