NOTE
Configuration numbers not listed are not used in this application. These items may appear when loading
configuration software to the controller but changes will not be recognized by the controller programming.
4.10 Controller Function Codes
CnF45
Low Humidity Enabled
Out
In
CnF46
Quench/liquid Injection Valve Type
nO=0=no
nC=1=nc
CnF47
Vent Position
OFF
UP, LOW, CUStOM
CnF49
OEM Reset Option
OFF
0-off,1-std, 2-spec, 3-cust
CnF50
Enhanced Bulb Mode Interface
0
0-out, 1-in
CnF51
Timed Defrost Disable
0
0-out, 1-in
CnF52
Oil Return Algorithm
0
0-out, 1-in
CnF53
Water Cool Oil Return Logic
0
0-out, 1-in
CnF55
TXV Boost Relay
0
0-out, 1-in
CnF56
TXV Boost Circuit
0
0-out, 1-in
CnF57
PWM Compressor Control
0
0-out, 1-in
CnF59
Electronic Evaporator Expansion Valve
0
0-out, 1-EC, 2-KE, 3-NA
CnF61
ACT ASC Control Enable
0
0-out, 1-in
CnF62
Extended Temperature Control Enable
0
0-out, 1-in
CnF63
CCPC Pre-trip/Tripstart Default State
0
0-on, 1-off
CnF64
Enable Fan Pulsing Logic
0
0-in, 1-out
CnF66
High Speed Evaporator Fan Option
0
0-off, 1-on
CnF67
Air Heaters
0
0-out, 1-in
Table 4–5 Controller Function Codes
Code
Title
Description
Note: If the function is not applicable, the display will read “-----”
Display Only Functions
- Cd01 through Cd26 are display only functions.
Cd01
Digital Unloader
Valve Closed (%)
Displays the DUV percent closed. The right display reads 100% when the valve
is fully closed. The valve will usually be at 10% on start up of the unit except in
very high ambient temperatures.
Cd03
Compressor Motor
Current
The current sensor measures current draw in lines L1 & L2 by all of the high volt
-
age components. It also measures current draw in compressor motor leg T3. The
compressor leg T3 current is displayed.
Cd04
Cd05
Cd06
Line Current,
Phase A
Line Current,
Phase B
Line Current,
Phase C
The current sensor measures current on two legs. The third unmeasured leg is
calculated based on a current algorithm. The current measured is used for con
-
trol and diagnostic purposes. For control processing, the highest of the Phase A
and B current values is used for current limiting purposes. For diagnostic pro
-
cessing, the current draws are used to monitor component energization.When
-
ever a heater or a motor is turned ON or OFF, the current draw increase/
reduction for that activity is measured. The current draw is then tested to deter
-
mine if it falls within the expected range of values for the component. Failure of
this test will result in a Pre-trip failure or a control alarm indication.
Cd07
Main Power Voltage
The main supply voltage is displayed.
Table 4–4 Controller Configuration Variables
Config
Title
Default
Option
Содержание Transicold 69NT40-561-001
Страница 2: ......
Страница 4: ......
Страница 14: ......
Страница 22: ......
Страница 36: ......
Страница 92: ......
Страница 159: ...7 47 T 340...
Страница 163: ...8 3 T 340 Figure 8 2 Schematic Diagram for Standard Unit Configuration Based on Drawing 62 11271 Rev A...
Страница 169: ...8 9 T 340 Figure 8 8 Schematic and Diagram for Lower Vent Position Sensor VPS Option...
Страница 170: ...T 340 8 10 Figure 8 9 Unit Wiring Diagram for Standard Unit Configuration With 3 Phase Condenser Fan Motors...
Страница 172: ...T 340 8 12 Figure 8 10 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater...
Страница 173: ...8 13 T 340 Unit Wiring Diagram for Single Phase Condenser Fan Motor and Optional Heater Based on Drawing 62 66721...
Страница 174: ...T 340 8 14 Figure 8 11 Unit Wiring Diagram for Configuration With eAutoFresh and Emergency Bypass Options...
Страница 176: ......
Страница 180: ......
Страница 181: ......