Auxiliary Heat Configuration (Heat Pumps)
Auxiliary heat configuration manages the settings for the heat pumps auxiliary heating
terminals (W1 and W2).
Auxiliary Heat Minimum On Time (Heat Pumps)
This will require the system to operate the auxiliary heat for a minimum time once it
has started regardless of demand in order to prevent short cycling.
This controls the
W1 and W2 terminals.
Default:
5 minutes
Options:
Between 1 and 20 minutes
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Operating
Thresholds > Auxiliary Heat Configuration > Auxiliary heat minimum
on time