background image

Содержание SYSTEM PILOT 33PILOT-01

Страница 1: ...and cause occupancy overrides A security feature is provided to limit access of features for unauthorized users INSTALLATION Location The System Pilot is the command center for the 3V control system...

Страница 2: ...nductors must be insulated with PVC PVC nylen vinyl Teflon or polyethylene An aluminum polyester 100 foil shield and an outer jacket of PVC PVC nylon chrome vinyl or Teflon with a minimum operating te...

Страница 3: ...Drill two 3h6 in mounting holes in wall where marked in Step 4 6 Secure mounting backplate to wall using two screws and anchors provided 7 Adjust length and routing of each wire to reach the terminal...

Страница 4: ..._uaJ Overr_de 35 in lb 4 Nm 80 110s 24VAC DC 50 60Hz 3VA 2W COM _ j_m 1 2 3 blk red wht C3 B Y BI O 0 0 0 0 0 0 0 0 oo T GND _2o PAT GND F 1 F 1 F 1 COM2 I I I I i i G G 6 5 4 3 2 1 Fig 2 System Pilot...

Страница 5: ...YP _ RED TYP ZONE CONTROLLER F SYSTEM PILOT IZONE CONTROLLER GND IBRIDGE RECOMMENDED Fig 3 Carrier Communicating Network Communication Bus Wiring _0 _ i q Fig 4 Recessed Mount Backplate WALL S_DE UP t...

Страница 6: ...ows the OAT vmiable value An exmnple of the OAT Display screen is shown in Fig 10 When the System Pilot is connected to the Zone Controller s local bus Comm2 the OAT display feature is disabled Mon SY...

Страница 7: ...FY knob changes one character at a time scrolling through the appropriate range of ASCII charactel_ From the Zone Controller Default screen the MODIFY knob _fllows the user to modify the set points Th...

Страница 8: ...NC DEC or MODIFY to modify the field fllen press SELECT again to attach If the System Pilot is aheady attached to the specified ad dress the System Pilot will display the message Reattach followed by...

Страница 9: ...al Bus Controller ID Generic controller CESR123456 99 Version 7 89 Bus Number 0 Element Number 123 Baud Rate 9600 Text Error messages Fig 15 Controller ID Screen Controller Name Alarm6 14 30 04 23 03...

Страница 10: ...ECT button is pressed and the current point is editable the System Pilot allows the user to modify the point NOTE For strings truncated for display NAVIGATE will adjust a sliding window of as many cha...

Страница 11: ...t write set points to the controller unless they have been changed IYomtheir original values Occupancy Override To initiate an override from the Zone Controller Default Screen if the Zone Controller s...

Страница 12: ...bled 1 to 1440 min Default Value 0 min ALARM ROUTING This decision is used to indicate which Carrier communicating network element will receive and process alarms sent by the System Pilot Tills decisi...

Страница 13: ...l time clock will adjust the time for the end of daylight saving time An entry of 0 will disable this feature Stop Back Allowable Entries 0 to 360 min Default Value 60 min Holiday HOLDYxxS Configurati...

Страница 14: ...t have to be in the same set point table The System Pilot reads the set points once per minute grad updates them upon user request from the Remote Attach Default Screen Cool Set Point Table Name Use t...

Страница 15: ...device while it is displaying the Remote Attach Default Screen Mode Calculation Allowable Entries Enable Disable Default Value Disable Supply Temp Variable Use this decision to specify the name of th...

Страница 16: ...o No or changes the default device the System Pilot will auto the SPT vmiable in the default device allowing it to return to its own value When the Communication Mode decision is changed from CCN to L...

Страница 17: ...s TYPE OF ACCESS LEVEL 1 LEVEL 2 LEVEL 3 LEVEL 4 From default screen Change set points if applicable Yes Yes Yes No Initiate timed override if applicable Yes Yes Yes No Show alternate display 3V TM co...

Страница 18: ...te Attach Bus Number Allowable Entries 0 to 239 Forcible No REMOTE ATFACH ELEMENT NUMBER This point dis plays the element number of the Remote Device that is configured in the Remote Attach Configurat...