6.5 - Unit start/stop control
The unit state is determined based on a number of factors,
including its operating type, active overrides, open contacts, , or
alarms triggered due to operating conditions.
The table given below summarises the unit control type
[ctrl_typ] and its running status with regard to the following
parameters:
■
Operating type:
This operating type is selected using the Start/
Stop button on the user interface.
LOFF
Local off
L-C
Local on
L-SC
Local schedule
REM
Remote
CCN
Network
TSTAT
Thermostat
IMPO
RTANT: When the unit is stopping or there is a demand to
stop the unit, compressors are stopped consecutively.
In case of emergency stop, all compressors are stopped at
the same time
.
Start/stop
force
command
[ROOF_S_S]:
Rooftop
start/stop force command can be used to control the unit state
in the Network mode.
-
Command set to stop: The unit is halted.
-
Command set to start: The unit runs in accordance with
schedule 1.
■
Remote start/stop contact status [Onoff_sw]:
Start/stop
contact status can be used to control the unit state in the
Remote operating type.
■
G:
This contact is used when unit is in thermostat
operating type
■
Start/stop schedule [roof_occ]:
Occupied or unoccupied
status of the unit.
■
Network emergency stop command [EMSTOP]:
If activated,
the unit shuts down regardless of the active operating type.
■
General alarm:
The unit shuts down due to failure.
Active operating type
Parameters status
Result
LOFF
L-
ON
L-SC
Rem
CCN
TSTAT
Start/stop
force
command
Remote
start/stop
contact
G
Start/stop
time schedule
Network
emergency
shutdown
General
alarm
Control
type
Unit
state
-
-
-
-
-
-
-
-
-
enabled
-
-
off
-
-
-
-
-
-
-
-
-
-
yes
-
off
active
-
-
-
-
-
-
-
-
-
-
local
off
-
-
active
-
-
-
-
-
unoccupied
-
-
local
off
-
-
-
active
-
-
-
OFF
-
-
-
remote
off
-
-
-
active
-
-
-
-
unoccupied
-
-
remote
off
-
-
-
-
active
-
disable
-
-
-
-
CCN
off
-
-
-
-
active
-
-
-
unoccupied
-
-
CCN
off
-
-
-
-
-
active
-
-
OFF
-
-
tstat
off
-
activ
e
-
-
-
-
-
disabled
no
local
on
-
-
active
-
-
-
-
occupied
disabled
no
local
on
-
-
-
active
-
On cooling
occupied
disabled
no
remote
on
-
-
-
active
-
-
On heating
occupied
disabled
no
remote
on
-
-
active
-
-
-
On auto
occupied
disabled
no
remote
on
-
-
-
active
-
enable
-
occupied
disabled
no
CCN
on
active
ON
tstat
on