T-362
4–38
AL56 Primary Return Sensor (RTS)
Cause:
Invalid Return Temperature Sensor (RTS) reading.
Component
Return Temperature Sensor (RTS)
Troubleshooting
Perform pre-trip P5.
Corrective Action
If P5 passes, no further action is required.
If P5 fails, replace the defective sensor as determined by P5. See Temperature
AL57 Ambient Sensor (AMBS)
Cause:
Invalid Ambient Temperature Sensor (AMBS) reading.
Component
Ambient Temperature Sensor (AMBS)
Troubleshooting
Test the AMBS. See Sensor Checkout Procedure
.
Corrective Action
Replace AMBS if defective. See Temperature Sensor Service
AL58 Compressor High Pressure Safety (HPS)
Cause:
High pressure safety switch remains open for at least one minute.
Component
High Pressure Switch (HPS)
Troubleshooting
Test the HPS. See Checking High Pressure Switch,
.
Corrective Action
Replace HPS if defective. See Sensor Replacement,
.
Component
Refrigeration System
Troubleshooting
Check unit for air flow restrictions.
Corrective Action
Clean or remove any debris from coils.
AL59 Heater Termination Thermostat (HTT)
Cause:
Heat Termination Thermostat (HTT) is open.
Component
Heat Termination Thermostat (HTT)
Troubleshooting
Check for 24 volts at test point TP10. If no voltage at TP10 after unit has reached
setpoint, HTT is open.
Corrective Action
Replace HTT if defective. See Sensor Replacement
AL60 Defrost Temperature Sensor (DTS)
Cause:
Failure of the Defrost Temperature Sensor (DTS) to open.
Component
Defrost Temperature Sensor (DTS)
Troubleshooting
Test the DTS; see Sensor Checkout Procedure
.
Corrective Action
Replace the DTS if defective. See Sensor Replacement
.
AL61 Heater Current Draw Fault
Cause:
Improper current draw during heat or defrost mode.
Component
Heater(s)
Troubleshooting
While in heat or defrost mode, check for proper current draw at heater contactors.
.
Table 4–5 Alarm Indications and Descriptions
Содержание PrimeLINE 69NT40-561-200
Страница 12: ......
Страница 18: ......
Страница 100: ......
Страница 182: ......
Страница 183: ...8 1 T 362 SECTION 8 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 1 LEGEND Standard Unit Configuration ...
Страница 184: ...T 362 8 2 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 2 Schematic Diagram ...
Страница 185: ...8 3 T 362 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 3 Unit Wiring Diagram Sheet 1 of 2 ...
Страница 186: ...T 362 8 4 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 4 Unit Wiring Diagram Sheet 2 of 2 ...
Страница 187: ...8 5 T 362 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 5 Legend Unit With Auto Transformer ...
Страница 188: ...T 362 8 6 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 6 Schematic Diagram Unit With Auto Transformer ...