Table 2 — Electrical Data
LEGEND
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR circuit breaker.
Canadian units may be fuse or circuit breaker.
2. Wire sizing amps are a sum of 125% of the compressor RLA plus
100% of indoor fan motor FLA.
3. Motors are protected against primary single phasing condition.
4. Indoor-fan motors are 3-phase motors of same voltage as unit.
Table 3 — Fan Electrical Data
LEGEND
NOTE: The FLA data listed in this table is for one fan only. When
calculating system FLA, evaporator fan and condenser fan must be
included.
UNIT
50XCA
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
NO. 1
COMPRESSOR
NO. 2
Min
Max
RLA
LRA
RLA
LRA
06
208/230-3-60
187
253
18.3
136
—
—
460-3-60
414
506
8.8
66
—
—
575-3-60
518
632
6.6
55
—
—
08
208/230-3-60
187
253
23.0
149
—
—
460-3-60
414
506
11.0
75
—
—
575-3-60
518
632
8.0
54
—
—
12
208/230-3-60
187
253
15.6
110
15.9
110
460-3-60
414
506
7.8
52
7.1
52
575-3-60
518
632
5.8
39
5.1
39
14
208/230-3-60
187
253
19.6
136
19.2
136
460-3-60
414
506
8.2
66
8.7
66
575-3-60
518
632
6.6
55
6.9
55
16
208/230-3-60
187
253
28.7
191
23.0
149
460-3-60
414
506
13.3
100
11.0
75
575-3-60
518
632
10.0
78
8.0
54
24
208/230-3-60
187
253
40.7
240
28.7
191
460-3-60
414
506
19.3
140
13.3
100
575-3-60
518
632
15.6
107
10.0
78
LRA
— Locked Rotor Amps
NEC
— National Electrical Code
RLA
— Rated Load Amps
MOTOR
CODE
MOTOR
HP
V-PH-Hz
VOLTAGE
RANGE
FLA
Min
Max
B
0.50
208/230-3-60
187
253
1.8/2.2
460-3-60
414
506
1.1
575-3-60
518
632
0.9
C
0.75
208/230-3-60
187
253
2.5/2.6
460-3-60
414
506
1.3
575-3-60
518
632
1.0
D
1.00
208/230-3-60
187
253
3.2/3.2
460-3-60
414
506
1.6
575-3-60
518
632
1.1
E
1.50
208/230-3-60
187
253
4.6/4.8
460-3-60
414
506
2.4
575-3-60
518
632
1.6
F
2.00
208/230-3-60
187
253
6.0/5.8
460-3-60
414
506
2.9
575-3-60
518
632
2.1
FLA
— Full Load Amps