62
ALARM CONFIG
Access: Home Screen
The Alarm Config screen (see Fig. 61) allows the user to view and
set the different trip points for the unit.
Fig. 61 — Alarm Config Screen
Click the
[
PREV]
softkey to return to the Home screen. See
Table 47 for screen function information.
OUTSIDE AIR RESET (TEMP RESET)
Access: Home Screen
The Outside Air Reset screen (see Fig. 62) allows the user to view
the existing reset air temperature. It also allows the user to change
the location of sensor, the type of sensor and the temperature reset
setpoint.
Fig. 62 — Outside Air Reset Screen
Table 46 — UPM2 Faults Screen Functions
FIELD / KEY
FUNCTION / INFORMATION
Reset UPM now?
(adjustable)
Allows the user to reset the Unit Protection
Module (UPM)
Current Fault
(non-adjustable)
Displays if the UPM has registered a fault
HP2 Faults (Total)
(non-adjustable)
Displays the number of High-Pressure
switch faults for Circuit 2 since the last
reset
HP2 Faults (Last hr)
(non-adjustable)
Displays the number of High-Pressure
switch faults for Circuit 2 in the last hour
LP2 Faults (Total)
(non-adjustable)
Displays the number of Low-Pressure
switch faults for Circuit 2 since the last
reset
LP2 Faults (Last hr)
(non-adjustable)
Displays the number of Low-Pressure
switch faults for Circuit 2 in the last hour
HP4 Faults (Total)
(non-adjustable)
Displays the number of High-Pressure
switch faults for Circuit 4 since the last
reset
HP4 Faults (Last hr)
(non-adjustable)
Displays the number of High-Pressure
switch faults for Circuit 4 in the last hour
LP4 Faults (Total)
(non-adjustable)
Displays the number of Low-Pressure
switch faults for Circuit 4 since the last
reset
LP4 Faults (Last hr)
(non-adjustable)
Displays the number of Low-Pressure
switch faults for Circuit 4 in the last hour
FRZ Faults (Total)
(non-adjustable)
Displays the number of Freeze alarms
since the last reset
FRZ Faults (Last hr)
(non-adjustable)
Displays the number of Freeze alarms in
the last hour
CON Faults (Total)
(non-adjustable)
Displays the number of Condensate
alarms since the last reset
CON Faults (Last hr)
(non-adjustable)
Displays the number of Condensate
alarms in the last hour
BRN Faults (Total)
(non-adjustable)
Displays the number of Brown Out alarms
since the last reset
BRN Faults (Last hr)
(non-adjustable)
Displays the number of Brown Out alarms
in the last hour
Reset UPM Alarms
(adjustable)
Allows the UPM alarms to be reset
Reset count now?
(adjustable)
Allows the number of UPM alarm counts to
be reset.
Enable UPM Alarms?
(adjustable)
Allows the UPM alarms to be enabled or
disabled.
Table 47 — Alarm Config Screen Functions
FIELD / KEY
FUNCTION / INFORMATION
High Discharge Air Trip
(adjustable)
Displays the current High Discharge Air Trip
setpoint
Low Leaving Water Trip
(adjustable)
Displays the current low leaving water trip
setpoint
High Leaving Water Trip
(adjustable)
Displays the current high leaving water trip
setpoint
Comp1 Runtime Trip (hrs)
(adjustable)
Displays the current Compressor 1
runtime trip setpoint in hours
Comp2 Runtime Trip (hrs)
(adjustable)
Displays the current Compressor 2
runtime trip setpoint in hours
Comp3 Runtime Trip (hrs)
(adjustable)
Displays the current Compressor 3
runtime trip setpoint in hours
Comp4 Runtime Trip (hrs)
(adjustable)
Displays the current Compressor 4
runtime trip setpoint in hours
Filter Alarm after 2000 hrs
runtime
(adjustable)
Displays the current setting for the filter
alarm in hours.
Use runtime to trip filter
alarm?
(adjustable)
Allows the user to receive an alarm after
the filter alarm setting has been exceeded.
[
Prev]
Softkey access to previous screen