8
heating/air conditioning output. The start/stop delays of the
blower must also be adjusted by positioning the DIP switches
on the electronic board. Refer to the following tables and the
wiring diagram, figure 8, in this manual for the proper settings:
Table 3: Heating Mode
SW1 – HEAT
DIP Switch Positions
1 2
POSITION
Input
USGPH
OFF OFF
A
0.70
ON OFF
B
0.55
OFF ON
C*
0.55
ON ON
D
ALL
Table 4: Air Conditioning Mode
SW2 – COOL
DIP Switch Positions
1 2
POSITION
Output
Tons
OFF OFF
A
3.0
ON OFF
B
2.5
OFF ON
C
2.0
ON ON
D
1.5
Table 5: CFM adjustment - All Modes
SW3 – ADJ (Adjustment)
DIP Switch Positions
1 2
POSITION
CFM HTG.
% increase
or decrease
CFM A/C
% increase
or decrease
OFF OFF
A
0%
0%
ON OFF
B
+10%
+10%
OFF ON
C
-10%
-10%
ON ON
D
N/A
0%
Table 6: Delay adjustments - Heating Mode
SW4 – Delay
DIP Switch Positions
1 2
POSITION
Input
USGPH
OFF OFF
A
0.70
ON OFF
B
0.55
OFF ON
C*
0.55
ON ON
D
ALL
2.11
INSTALLATION OF ACCESSORIES
WARNING
Electrical shock hazard.
Turn OFF electrical power at the fuse box or service
panel before making any electrical connections and
ensure a proper ground connection is made before
connecting line voltage.
Failure to do so can result in death or bodily injury.
2.11.1
H
UMIDIFIER
(HUM)
The 120 VAC HUM terminal on the electronic board of the
blower is tied directly to terminal 8 of the 9-terminal
connector of the electronic board. It supplies 120 VAC
electric power when the burner is in operation.
A 24 VAC signal can also be supplied from the W and C
terminals on the blower electronic board to activate a
switching relay.
Also refer to the instructions supplied with the accessory.
2.11.2
E
LECTRONIC AIR
C
LEANER
(EAC)
The EAC terminal on the electronic board supplies 120
VAC when the blower is operating in the heating or air
conditioning mode. This signal can be used to activate an
electronic air cleaner that is not equipped with an air flow
switch. If the cleaner is equipped with an air flow switch,
the S terminal on the electronic board can be used to
provide a constant supply of 120 VAC.
Also refer to the instructions supplied with the accessory.
2.11.3
A
IR
C
ONDITIONER
(
OR
H
EAT
P
UMP
)
An air conditioning coil has to be installed on the supply
air side ONLY.
WARNING
Poisonous carbon monoxide gas hazard.
Install the evaporator coil on the supply side of the
furnace ducting ONLY.
An evaporator coil installed on the return air side of
the ducting can cause condensation to form inside
the heat exchanger, resulting in heat exchanger
failure. This in turn, can result in death, bodily injury
and/or property damage.
A clearance of 15 cm (6") is required between the bottom
of the coil drain pan and the top of the heat exchanger. If
a heat pump is installed, a “dual-energy” thermostat, or
other control is recommended, in order to prevent the
simultaneous operation of the furnace and the heat pump.
It also prevents a direct transition from heating by way of
the heat pump to heating with oil. Refer to the thermostat
instructions or those of another control used for the proper
wiring.
If a coil blower compartment is used, install air tight,
motorized and automatic air dampers. Cold air coming
from the coil and passing across the furnace can cause
condensation and shorten the life of the heat exchanger.
Содержание OBL098
Страница 16: ...16 Figure 6 Furnace Dimensions ...
Страница 17: ...17 Figure 7 Wiring Diagram 4 Speed Motor PSC ...
Страница 18: ...18 Figure 8 Wiring Diagram Variable Speed Motor ECM ...
Страница 19: ...19 Figure 9 Parts List With 4 Speed motor PSC B50082E ...
Страница 21: ...21 Figure 10 Parts List With variable speed motor ECM B50083E ...
Страница 23: ......
Страница 24: ......
Страница 29: ...Figure 8 Diagramme électrique Moteur vitesse variable ECM 20 ...
Страница 31: ...Figure 6 Dimensions de la fournaise 18 ...