Standard Range Zone Pressure Multi-Sensor (ZPM)
Installation and Operation
Specifications subject to change without notice.
1 of 5
Catalog No. 11-808-711-01
#38592
–
1/10/19
Overview
The Zone Pressure Multi-Sensor
(Part #NSB-ZPM-SR-ST-D) is the
most flexible pressure sensor on
the market. Output, range, units,
directionality, and response time
are quickly set in the field with no
tools, no power, and no small
components.
The LCD display helps with
troubleshooting because it displays
the actual differential pressure
over the entire operational range
regardless of which pressure
range is selected for output to the
system controller. Three LEDs on
the face of the unit indicate when
the pressure is “Out of Range
Low”, “In Range”, or “Out of
Range High”.
Bulkhead fitting
for static tube
Mounting
screws
Deadhead
tubing
Static
tube
screws
Cover latch
screw
Conduit
foam plug
Static tube
and hose
with surge
damper
Specifications
Power:
7 to 40 VDC for 4 to 20 mA Output
7 to 40 VDC or 18 to 32 VAC for 0 to 5 or 1 to 5 V Output
13 to 40 VDC or 18 to 32 VAC for 0 to 10 or 2 to 10 V Output
Power Consumption:
20 mA max, DC only at 4 to 20 mA Output
4.9 mA max DC at 0 to 5 VDC or 0 to 10 VDC Output
0.12 VA max AC at 0 to 5 VDC or 0 to 10 VDC Output
Load Resistance:
4 to 20 mA Output
850 Ω Maximum @ 24 VDC
0 to 5 V or 0 to 10 V output 6K to 10KΩ minimum
Accuracy for Standard Pressure Ranges at 72°F:
±0.25% of range
Stability:
±0.25% F.S. per year
Port Size:
1/4” tubing (1/8” to 3/16” I.D.)
Environmental Operating Range:
-
4 to 140°F (-20 to 60°C)
Storage Temperature:
-40 to 203°F (-40 to 95°C)
Temperature Error Standard Range:
Figure 2: ZPM Dimensions
0.01% FS/°F (0.02% FS/°C)
(±1.0” W.C @-4 to 140ᵒF (-20 to 60°C)
Overpressure:
Proof: 300.1 WC (10.83 PSI)
Burst: 512.6 WC (18.5 PSI)
Wiring:
2 wires (4 to 20mA Current loop)*
3 wires (AC or DC powered, Voltage out)*
Humidity:
0 to 95% RH, non-condensing
Port Size:
1/4” tubing (1/8” to 3/16” I.D.)
Encl. Material:
UV-resistant Polycarb., UL94, V-0
Enclosure Rating:
IP44, NEMA 2
Figure 1:
ZPM unit and
associated parts
Selectable Standard Ranges
Inches WC
Pascals
0 to 1.00.............................. 0 to 250
0 to 2.00.............................. 0 to 300
0 to 2.50.............................. 0 to 500
0 to 3.00........................... 0 to 1,000
0 to 5.00........................... 0 to 1,250
-1.00 to 1.00 .................. -250 to 250
-2.00 to 2.00 .................. -300 to 300
-2.50 to 2.50 .................. -500 to 500
-3.00 to 3.00 ............ -1,000 to 1,000
-5.00 to 5.00 ............ -1,250 to 1,250