background image

 

AIR CONDITIONER (MULTI TYPE)

Indoor Unit

Model name:

High Wall Type

MMK-AP0073H2UL
MMK-AP0093H2UL
MMK-AP0123H2UL
MMK-AP0153H2UL
MMK-AP0183H2UL
MMK-AP0243H2UL

Installation Manual

Installation Manual

1

English

Manuel d’installation

32

Français

+001111053901_00Ta.book  Page 1  Monday, January 17, 2011  11:35 AM

Содержание MMK-AP0073H2UL

Страница 1: ...High Wall Type MMK AP0073H2UL MMK AP0093H2UL MMK AP0123H2UL MMK AP0153H2UL MMK AP0183H2UL MMK AP0243H2UL Installation Manual Installation Manual 1 English Manuel d installation 32 Fran ais 00111105390...

Страница 2: ...Applicable Controls 21 11 Test Run 24 12 Troubleshooting 26 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the in...

Страница 3: ...llation plate 1 Wireless remote control 1 Battery 2 Remote control holder 1 Mounting screw 0 16 4 mm 1 0 25 mm 6 Pan head wood screw 1 8 3 1 mm 0 6 16 mm 2 Screw 0 16 4 mm 0 4 10 mm 2 Heat insulator 1...

Страница 4: ...a qualified installer or service person is allowed to do installation work Inappropriate installation may result in water leakage electric shock or fire Do not use any refrigerant different from the o...

Страница 5: ...the valve open the compressor sucks air and the refrigeration cycle is overpressurized which may cause a burst or injury CAUTION THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT R410A WHICH DOES NO...

Страница 6: ...ace close to a machine generating high frequency Place where the discharged air blows directly into the window of the neighbor house Outdoor unit Place where noise of the outdoor unit is easily transm...

Страница 7: ...Wall Insert the cushion between the indoor unit and wall and tilt the indoor unit for better operation Do not allow the drain hose to get slack Cut the piping hole sloped slightly Make sure to run th...

Страница 8: ...y with the following rules to prevent damage of the indoor units and human injury Do not put a heavy article on the indoor unit Even units are packaged Carry in the indoor unit as it is packaged if po...

Страница 9: ...screw do not use the anchor bolt hole Otherwise the unit may fall down and result in personal injury and property damage CAUTION Failure to firmly install the unit may result in personal injury and pr...

Страница 10: ...of the front panel for the bottom left or right connection with a pair of nippers 3 Changing drain hose For leftward connection bottom leftward connection and rear leftward connection s piping it is n...

Страница 11: ...knife or a marking off pin cut them with a pair of nippers or an equivalent tool Remove the drain hose 1 Remove the front panel 2 Remove the screws of drain hose 3 Pull out the drain hose Fix the drai...

Страница 12: ...ing pipe through the pipe hole connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them CAUTION Arrange pipes so that any pipe does not stick out of the rear plate of th...

Страница 13: ...e screwed to the installation plate 7 Drainage 1 Run the drain hose sloped downwards NOTE Hole should be made at a slight downward slant on the outdoor side 2 Put water in the drain pan and make sure...

Страница 14: ...nit Flaring Cut the pipe with a pipe cutter Remove burrs completely Remaining burrs may cause gas leakage Insert a flare nut into the pipe and flare the pipe As the flaring sizes of R410A differ from...

Страница 15: ...eck test evacuation addition of refrigerant and gas leak check refer to the Installation Manual attached to the outdoor unit REQUIREMENT Do not supply power to the indoor unit until the leak check tes...

Страница 16: ...he tip of the pencil 00 will be shown on the display 4 Push during pushing B will be shown on the display and 00 will be disappear and the air conditioner will turn OFF The wireless remote control B i...

Страница 17: ...ect 208 230 V power to the terminal blocks U1 U2 A B etc for control wiring Otherwise the system will fail Perform the electric wiring so that it does not come to contact with the high temperature par...

Страница 18: ...Minimum Circuit Amps MOCP Maximum Overcurrent Protection Amps Model Power Supply Voltage Range V MCA MOCP Min Max A A MMK AP0073H2UL 208 230V 1 60Hz 187 253 0 3 15 MMK AP0093H2UL 0 3 15 MMK AP0123H2U...

Страница 19: ...al Outdoor Power supply Circuit breaker Circuit breaker Header outdoor unit Follower outdoor unit Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring be...

Страница 20: ...inal block and secure then tightly with screws Strip off the wire approx 0 4 9 mm to connect Remote control wire and control wire L1 L2 Clamp base Terminal Cover Cord clamp Screw Ground screw Screw Sc...

Страница 21: ...m attached inside the front panel Check local electrical cords and also any specific wiring instructions and limitations Do not catch the control and wired remote control wires when installing the cla...

Страница 22: ...g Stop the air conditioner before making settings Procedure 1 Push button and temp setup button simultaneously for 4 seconds or more After a while the display flashes as shown in the figure Confirm th...

Страница 23: ...remote control is accepted Filter sign setting According to the installation condition the lighting time of the filter sign Notification of filter cleaning can be changed Follow to the basic operation...

Страница 24: ...maximum 8 units The wired remote control only can control a group control The wireless remote control is unavailable for this control For wiring procedure and wires of the individual line Identical re...

Страница 25: ...en if the operation stops by thermo OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION Do not use the fo...

Страница 26: ...d outdoor units 1 When is pushed button for 10 seconds or more Pi sound is heard and the operation changes to a forced cooling operation After approx 3 minutes a cooling operation starts forcedly Chec...

Страница 27: ...and stop status Procedure 1 Push and buttons simultaneously for 4 seconds or more the following display appears If Service check is displayed the mode enters in the error log mode 01 Order of error l...

Страница 28: ...between indoor and remote control Detected at remote control side Remote control E02 Remote control transmission error Remote control E03 Communication error between indoor and remote control Detecte...

Страница 29: ...T Outdoor pressure sensor miswiring Pd Ps I F F22 F22 ALT TD3 error I F F23 F23 ALT Ps sensor error I F F24 F24 ALT Pd sensor error I F F29 SIM Indoor other error Indoor F31 F31 SIM Indoor EEPROM erro...

Страница 30: ...other than indoor unit with priority I F L07 SIM Group line in individual indoor unit Indoor L08 L08 SIM Indoor group Address unset Indoor I F L09 SIM Indoor capacity unset Indoor L10 L10 SIM Outdoor...

Страница 31: ...Inverter DC voltage error outdoor unit fan Caution Although letters 0 to F appear at locations indicated by please ignore them ALT Outdoor fan IPDU error IPDU P26 P26 01 Comp 1 side 02 Comp 2 side 03...

Страница 32: ...e 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amou...

Страница 33: ...0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 500...