i-Vu Open Link
5
To wire for power
1
Make sure the i-Vu Open Link’s power switch is in the
OFF
position to prevent it from powering up before
you can verify the correct voltage.
2
Remove power from the power supply.
3
Pull the screw terminal connector from the controller's power terminals labeled
24V ac/dc
and
Ground
.
4
Connect the transformer wires to the screw terminal connector.
5
Apply power to the power supply.
6
Measure the voltage at the i-Vu Open Link’s power input terminals to verify that the voltage is within the
operating range of 21.6 – 26.4 Vac or 23.4 - 28.6 Vdc.
7
Insert the screw terminal connector into the i-Vu Open Link's power terminals.
8
Turn
on
the i-Vu Open Link's power.
9
Verify that the Run LED (a dot in the lower right corner of the
Module Status
LED) begins blinking. The
Module Status
LED will display
8
for about 5 seconds and then reverts to
0,
until Open controllers have
been discovered and uploaded. There is a chase pattern when the controller is running with no errors.
Wiring for communications
The i-Vu Open Link has multiple ports. See table below for port descriptions.
Port
Protocol
Port
type(s)
Baud rate(s)
Use for
BACnet/IP
Ethernet
Port E1
Ethernet
10 Mbps
100 Mbps
LAN connection
S1
BACnet MS/TP
EIA-485
(2-wire)
DIP Switch selectable:
•
9600 bps
•
19.2 kbps
•
38.4 kbps
•
76.8 kbps (default)
Open network connection
S2
Modbus
LonWorks
EIA-485
EIA-232
DIP switch selectable
Third-party communication
N/A
Local
Access
Rnet
115.2 kbps
•
Router configuration
•
System start-up and
troubleshooting with
Carrier Tools