Installing the MPC Open XP
MPC Open XP
MPC Open XP IO48/816
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
All rights reserved
21
Shielding
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire, terminated
at controller
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
ZS sensor overview
ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO
2
, or VOC. ZS
Sensors are wired to the Rnet port on most Carrier controllers.
REQUIREMENTS
•
A v6.0 or later i-Vu® system
•
v6-xx-xxx or later controller drivers
You can use the following ZS sensors:
•
ZS Standard
•
ZS Plus
•
ZS Pro
•
ZS Pro-F
An Rnet can consist of the following devices wired in a daisy-chain or star configuration:
•
Up to 15 ZS sensors if the controller contains multiple control programs for the sensors
•
One Equipment Touch
•
You cannot have SPT sensors and ZS sensors on the same Rnet.
For basic user instructions, see the
ZS Sensor User Guide
. For detailed installation instructions, see the
ZS
Sensors Installation Guide
.
SPT sensor overview
The SPT sensor is a wall-mounted space temperature sensor that monitors room temperature.
The MPC Open XP supports the following:
•
SPT Standard
•
SPT Plus
•
SPT Pro
•
SPT Pro Plus