Troubleshooting
i-Vu® Open Router
CARRIER CORPORATION ©2020
Installation and Start-up Guide
All rights reserved
26
Other LED's show the status of certain functions.
If this LED is on...
Status is...
Power
The i-Vu® Open Router has power.
Link
The i-Vu® Open Router is connected to the Ethernet
LAN
The Ethernet port is transmitting or receiving data
100
The connection speed is 100 Mbps. If LED is not lit, the connection speed is 10
Mbps.
S2 Tx
The i-Vu® Open Router is transmitting data on the Port S2 network
S2 Rx
The i-Vu® Open Router is receiving data from the Port S2 network
Archive Valid
The i-Vu® Open Router's memory backup is valid
S1 (BACnet) Tx
The i-Vu® Open Router is transmitting data to the MS/TP (Open) network
S1 (BACnet) Rx
The i-Vu® Open Router is receiving data to the Open network
Brownout
Low-level incoming power
Battery low
The battery is low
To get the serial number
If you need the i-Vu® Open Router's serial number when troubleshooting, the number is on:
•
A laser-etched number and QR code on the inside circuit board
•
a sticker on the back of the main controller board (prior to 2019)
•
a Module Status report (Modstat) under
Core
(or
Main
)
board hardware
To obtain a modstat in the i-Vu® interface:
1
Select the i-Vu® Open Router in the navigation tree.
2
Right-click and select
Module Status
.