March 2021
Page 47 of 143
59812-K007 Rev 17
Business Confidential
Figure 55
Control Unit Membrane
c.
The Green LED above the button pressed will now be flashing. The Control Unit will
automatically store this new Modbus address.
d.
When the address has been changed, the Control Unit returns to normal operation and indicates
the number of detectors connected.
Repeat the above for the number of Control Units installed per system.
After the addresses have been changed, please ensure that both EOL jumpers are fitted to the last
Control Unit only, all other Control Units need to have both the EOL jumpers removed.
Refer Figure 8 for EOL jumper positions.
NOTE: The Control Units 24Vdc Power Supply needs to be removed for a period of 10sec and
re-applied to ensure Modbus address changes are recognized on the Modbus network.
Once all Control Units have the correct Modbus addresses, the Remote Display Unit will need to be
programmed to detect the required number of engines on the system (refer Section 2.10.3)
2.10.2
Setting the Modbus address via the USB connection.
To change the Modbus address via the USB connection on the PCB (Refer Figure 56)
a.
Connect the 24Vdc power supply to the Control Unit to be changed.
b.
Connect the USB-B end to the USB socket located on the PCB inside the Control Unit (refer
Figure 56)
Press required numerical button for 1sec
Current Modbus address flashing
Содержание Graviner Mk7
Страница 26: ...March 2021 Page 15 of 143 59812 K007 Rev 17 Business Confidential Figure 10 Detector Head Installation ...
Страница 42: ...March 2021 Page 31 of 143 59812 K007 Rev 17 Business Confidential Figure 29 Wiring Drawing ...
Страница 129: ...March 2021 Page 118 of 143 59812 K007 Rev 17 Business Confidential 6 6 1 CONTROL UNIT Figure 182 Control Unit Spares ...
Страница 149: ...March 2021 Page 138 of 143 59812 K007 Rev 17 Business Confidential ...
Страница 152: ...March 2021 Page 141 of 143 59812 K007 Rev 17 Business Confidential ...