Figure 49
Detector Names Saved
To return to the Engine Screen, Figure 46
To set the individual Detector parameters, press the button under the mg/l display for the required
detector.
Figure 50
Detector Selection
Figure 51
Detector Status Screen
Press the up and down arrows to select the desired Alarm and Pre-Alarm Levels.
Slow/Shutdown Alarm Limits
1.3 2.4mg/l, default 1.8mg/l
Pre-Alarm Limits
0.5 1.2mg/l, default 0.9mg/l