Nov-21
Page 69 of 132
59812-K001 Rev 10
3.5.5
Backup Alarm
Tests the Backup Alarm signal between each detector and the Control Panel.
Select 5. Backup Alarm
A short beep maybe heard from the Control Panel buzzer while the connection from each detector is
tested.
Figure 86
Backup Alarm Test
If the Backup Alarm test is completed successfully the display will return to the Test Menu. If a fault is
detected a Backup Alarm Fault will be indicated on the display and the failed detector is listed.
3.5.6
Optics
Instructs all detectors to perform an optics test to ensure that oil contamination within the detector
sample chamber is within acceptable limits.
Select 6. Optics
This test may take up to 30 seconds to complete.
Figure 87
Optics Test
If the Optics test is completed successfully the display will return to the Test Menu. If a fault is detected
either an LED Average Fault or a Detector Fault will be indicated on the display and the failed detector
is listed.
3.5.7
Detector Alarm
Simulates an oil mist alarm from a specified detector. This test does not operate the Shutdown /
Slowdown Relay.
Select 7. Detector Alarm
Содержание Graviner Mk6
Страница 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Страница 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Страница 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Страница 30: ...Nov 21 Page 30 of 132 59812 K001 Rev 10 Figure 13 Detector Head Installation Short Sample Pipe ...
Страница 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Страница 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Страница 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Страница 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Страница 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...
Страница 129: ...Nov 21 Page 129 of 132 59812 K001 Rev 10 ...