Carrier GA7T Скачать руководство пользователя страница 6

GA7T: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

Airflow Selections (ECM Furnaces)

The ECM Furnaces provide blower operation to match the capacities of

the  compressor  during  high  and  low  stage  cooling  operation.  Tap

selections on the furnace control board enable the installing technician to

select  the  proper  airflows  for  each  stage  of  cooling.  Below  is  a  brief

summary of the furnace airflow configurations

1. The Y2 call for high stage cooling energizes the “Cool” tap on the

control board. The grey wire from cool tap is connected to tap 5 on

the  motor.  Refer  to  the  furnace  Product  Data  to  find  the

corresponding airflow. If the airflow setting for high cooling needs

to be switched from tap 5 to a different tap, jumper a connection

from  the  cool  tap  to  the  desired  tap  so  that  the  Y2  signal  is

communicated via the cool tap to the desired speed tap.

2. The Y1 call for low stage cooling energizes the “Fan” tap on the

control board. The red wire from the fan tap is connected to tap 1 on

the  motor.  Refer  to  the  furnace  Product  Data  to  find  the

corresponding airflow. If the airflow setting for low cooling needs

to be switched from tap 1 to a different tap, jumper a connection

from  the  Fan    tap  to  the  desired  tap  so  that  the  Y1  signal  is

communicated  via  the  Fan  tap  to  the  desired  speed  tap.  The Y1

setting will also govern the continuous fan airflow for the furnace.

Refer to the literature for the furnace for further details.

Airflow Selection for Variable Speed Furnaces

The  variable  speed  furnaces  provide  blower  operation  to  match  the

capacities  of  the  compressor  during  high  and  low  stage  cooling

operation. The furnace control board allows the installing technician to

select the proper airflows for each stage of cooling. Below is a summary

of required adjustments. See  furnace installation instructions for more

details: 

1. Turn  SW1--5  ON  for  400  CFM/ton  airflow  or  OFF  for  350

CFM/ton airflow.  Factory default is OFF.

2. The A/C DIP switch setting determines airflow during high stage

cooling operation. Select the A/C DIP switch setting corresponding

to  the  available  airflow  shown  in  the  furnace  Installation

Instructions that most closely matches the required airflow shown

in the air conditioning Product Data for HIGH speed.

3. The  CF  DIP  switch  setting  determines  airflow  during  low  stage

cooling operation. Select the CF DIP switch setting corresponding

to  the  available  airflow  shown  in  the  furnace  installation

instructions that most closely matches the required airflow shown

in the air conditioning Product Data for LOW speed. If a higher or

lower continuous fan speed is desired, the continuous fan speed can

be  changed  using  the  fan  switch  on  the  thermostat.  Refer  to  the

furnace  Installation  Instructions  for  details  of  how  to  use  this

feature.

Airflow Selection for FV4C Fan Coils

The FV4C provides high- and low-stage blower operation to match the

capacities of the compressor at high- and low-stage. 
To  select  recommended  airflow,  refer  to  the  FV4C  Installation

Instructions. The FV4C utilizes a control board that allows the installing

technician  to  select  proper  airflows.  This  fan  coil  has  an  adjustable

blower-off delay factory set at 90 sec. for high- and low-stage blower

operation.

Install Electrical Accessories

Refer  to  the  individual  instructions  packaged  with  kits  or  accessories

when installing.

Start-Up

Follow these steps to properly start up the system:

1. After system is evacuated, fully back seat (open) liquid and vapor

service valves.

2. Unit is shipped with valve stem(s) front seated (closed) and caps

installed. Replace stem caps after system is opened to refrigerant

flow  (back  seated).  Replace  caps  finger-tight  and  tighten  with

wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Ensure that set point is

below  indoor  ambient  temperature  and  is  set  low  enough  to

energize high stage. In order to start the system in high stage, refer

to the literature for the installed thermostat and adjust the set point

so that the differential between the room temperature and the set

temperature energizes Y2.

5. Set  room  thermostat  to  COOL  and  fan  control  to  ON  or AUTO

mode, as desired. 

6. Operate  unit  for  15  minutes. Verify  system  refrigerant  charge  by

measuring  the  sub-cooling  and  comparing  with  the  published

sub-cool on the rating plate.

System Function And Sequence Of Operation

This model utilizes a 2-stage cooling indoor thermostat. With a call for

first  stage  cooling,  the  outdoor  fan  and  low-stage  compressor  are

energized.  If  low-stage  cannot  satisfy  cooling  demand,  high-stage  is

energized by the second stage of indoor thermostat. After second stage is

satisfied,  the  unit  returns  to  low-stage  operation  until  first  stage  is

satisfied or until second stage is required again. 
When  both  first  stage  and  second  stage  cooling  are  satisfied,  the

compressor  will  shut  off.  Therefore,  with  first  stage  of  cooling Y1  is

powered on; and with second stage of cooling Y1 and Y2 are powered

on.    When  a  2-stage  unit  is  operating  at  low-stage,  system  vapor

(suction) pressure will be higher than a standard single-stage system or

high-stage operation. 

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury, equipment

damage or improper operation.

?

• Do not overcharge system with refrigerant.

• Do not operate unit in a vacuum or at negative pressure.

• Compressor dome temperatures may be hot.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal  injury.
Wear  safety  glasses,  protective  clothing,  and  gloves  when  handling

refrigerant and observe the following:

?

 Front seating service valves are equipped with Schrader valves.

Содержание GA7T

Страница 1: ...city 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tubes through the wall seal opening with RTV or other pliable silicon based caulk See Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7 Do not suspend refrige...

Страница 2: ...edown Knockout Locations Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Rated tubing diameters shown in Table 1 are recommended up to 80 ft 24 38 m See Product Data for acceptable alternate vapor diameters and associated capacity losses For tubing requirements beyond 80 ft 24 38 m substantial ...

Страница 3: ...uum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes See Fig 4 A95424 Fig 4 Deep Vacuum Graph Final Tubing Check IMPORTANT ...

Страница 4: ...ass 2 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power requirement Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required Final Wiring Check IMPO...

Страница 5: ...e R 410A refrigerant Air Conditioner A09278 A09279 Fig 7 Generic Wiring Diagrams See thermostat Installation Instruction for specific unit combinations A09306 Thermidistat w Variable Speed Fan Coil 2 Stage Air Conditioner Thermidistat w Variable Speed Furnace 2 Stage Air Conditioner Single Stage Furnace with 2 Stage Air Conditioner 2 Stage Thermostat with Single Stage Furnace and 2 Stage Air Condi...

Страница 6: ...o the furnace Installation Instructions for details of how to use this feature Airflow Selection for FV4C Fan Coils The FV4C provides high and low stage blower operation to match the capacities of the compressor at high and low stage To select recommended airflow refer to the FV4C Installation Instructions The FV4C utilizes a control board that allows the installing technician to select proper air...

Страница 7: ...d then be appropriate for the system to achieve rated capacity The charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range NOTE If line length is beyond 80 ft 24 38 m or greater than 20 ft 6 10 m vertical separation See Long Line Guideline for special charging requirements Final Checks IMPORTANT Before leaving job be sure to do...

Страница 8: ... an internal pressure relief IPR which relieves discharge gas into compressor shell when differential between suction and discharge pressures exceed 550 625 psi The compressor is also protected by an internal overload attached to motor windings Compressor Control Contactor The contactor has a 24 volt coil and is controlled by Y1 input from the thermostat CARE AND MAINTENANCE For continuing high pe...

Отзывы: