Installation Instructions
NOTE:
Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or
use can cause explosion, fire, electrical shock, or other conditions which
may cause death, personal injury or property damage. Consult a
qualified installer, service agency, or your distributor or branch for
information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product.
Refer to the individual instructions packaged with kits or accessories
when installing.
Follow all safety codes. Wear safety glasses, protective clothing and
work gloves. Have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in literature and
attached to the unit. Consult local building codes and the current editions
of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code
CSA C22.1.
Recognize safety information. This is the safety-alert symbol . When
you see this symbol on the unit and in instruction manuals, be alert to the
potential for personal injury.
Understand the signal words
DANGER
,
WARNING
, and
CAUTION
.
These words are used with the safety-alert symbol.
DANGER
identifies
the most serious hazards which
will
result in severe personal injury or
death.
WARNING
signifies hazards which
could
result in personal
injury or death.
CAUTION
is used to identify unsafe practices which
may
result in minor personal injury or product and property damage.
NOTE
is used to highlight suggestions which
will
result in enhanced
installation, reliability, or operation.
INTRODUCTION
FZ4A models are R-410A Fan Coils designed for installation flexibility.
These units leave the factory compliant with low leak requirements of
less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4% cabinet
leakage rate at 0.5 inches W.C. when tested in accordance with
ASHRAE 193 standard.
A TXV is used on FZ4ANP(024-061). All FZ4A fan coils use a
multi-tap ECM motor for efficiency. These units have be designed for
upflow, downflow (kit required), and horizontal orientations, including
manufactured and mobile home applications.
These units require a field supplied air filter, and are designed
specifically for R-410A refrigerant air conditioners and heat pumps as
shipped. These units are available for systems of 24,000 through 60,000
BTUh nominal cooling capacity. Factory- authorized, field - installed
electric heater packages are available in sizes 5 through 30kW. See
Product Data literature for all available accessory kits.
HEATER PACKAGES
This unit may or may not be equipped with an electric heater package.
For units not equipped with factory-installed heat, a factory-approved,
field-installed, UL listed heater package is available from your
equipment supplier. See unit rating plate for a list of factory-approved
heaters. Heaters that are not factory approved could cause damage which
would not be covered under the equipment warranty. If fan coil contains
a factory-installed heater package, minimum circuit ampacity (MCA)
and maximum fuse/breaker may be different than units with a same size
field-installed accessory heater. The difference is not an error and is due
to calculation differences per UL guidelines.
INSTALLATION
CHECK EQUIPMENT
Unpack unit and move to final location. Remove carton taking care not
to damage unit. Inspect equipment for damage prior to installation. File
claim with shipping company if shipment is damaged or incomplete.
NOTE:
If the door gasket is damaged or missing, the unit may not meet
the ASHRAE 193 standard for cabinet air leakage. Contact your supplier
and order kit #344994-751.
Locate unit rating plate which contains proper installation information.
Check rating plate to be sure unit matches job specifications.
MOUNT UNIT
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space
for wiring, piping, and servicing unit.
IMPORTANT:
When unit is installed over a finished ceiling and/or
living area, building codes may require a field-supplied secondary
condensate pan to be installed under the entire unit. Some localities may
allow as an alternative, the running of a separate, secondary condensate
line. Consult local codes for additional restrictions or precautions.
NOTE:
Nuisance sweating may occur if the unit is installed in a high
humidity environment with low airflow.
UPFLOW INSTALLATION
If return air is to be ducted through a floor, set unit on floor over opening
and use 1/8 to 1/4-in (3 to 6 mm) thick fireproof resilient gasket between
duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per
dimensions (
). A field-supplied bottom closure is required.
FZ4ANP
FAN COILS
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to maintain proper clearances could result in personal injury or
death.
Before installing or servicing unit, always turn off all power to unit.
There may be more than 1 disconnect switch. Turn off accessory heater
power if applicable. Lock out and tag switch with a suitable warning
label.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts.